GB - 3
42 WHC/AQUASMART
ENGLISH
Exposure to direct sunshine, when the unit is operating in cooling
mode; always use shutters or shades.
Positions too close to heating sources which may damage the unit.
Connecting condensate piping to sewage system drain without
appropriate trap. Trap height must be calculated according to the unit
discharge head in order to allow sufficient and continuous water evacuation.
Only partial insulation of the piping.
Installation not correctly levelled which will cause condensate
dripping.
Flattening or kinking the refrigerant pipes or condensate pipes.
Any obstruction of the unit air outlet or return.
Exposure to oil vapours.
Installation in areas with high frequency waves.
Any rise in the condensate drain piping.
Horizontal condensate drain piping with less than 2% slope.
Warnings: avoid…