Table III: Operating limits
Water circuit
Maximum water-side pressure Minimum entering water temperature: 6°C
1400 kPa (142 m WG) Maximum entering water temperature: 60°C
Indoor temperature
Minimum temperature: 5°C
(1)
Maximum temperature: 32°C
Power supply Nominal single-phase voltage
230V ~ 50Hz - min. 198V - max. 264V
Ref. Description Q.ty Use
Unit
1 Installation manual 1 Unit installation
Hanging panel / valve kit
1 Screw anchors and screws 4 + 4 Fixing the hanging panel to the wall
3 Screw anchors and screws
4 Screw 1 Safety screw
Minimum clearances (mm)
20
20
80
Table II: Material supplied
(1)
If the outdoor temperature can go down to 0°C, it is advisable to empty the water circuit to avoid breaks caused by ice (see paragraph on water
connections).