GB - 6
AQUASMART Room Controller
Room Controller configuration
• Press either the “UP” or “DOWN” button until the appropriate
number is displayed. Please refer to the following table for
proper selection:
Unit type Application Size Selected
value
Hi-Wall 42WHC/WHE
All All 1
Cassette 42GW All All 3
Fan Coil 42Y Vertical All 4
Fan Coil 42Y Horizontal All 5
Above ceiling 42JW All All 5
Above ceiling 42EL All All 5
If your unit is not included in the above models, refer to unit
installation manual to determine the selected value.
An error in the selected value, causes a malfunction or
absent swing of the louver and a bad comfort in the
heating mode.
• To end “
UNIT CONFIGURATION” mode do not press any buttons for
10 seconds.
4- WINDOW CONTACT SELECTION
It is possible to configure the window contact in the NO
condition (normally open) or in the NC (normally closed)
condition.
To perform this configuration, proceed as follows:
• Press and hold down the “
UP” and “DOWN” keys at the same
time for around 5 seconds.
• Press “
UP” button until “-4” is displayed.
• Press the “
MODE” button to select the mode.
up
down
up
down
up
down
• Press the “UP” or “DOWN” per passare dalla modalitàbutton to
go from the “O” mode (open) to the “C” mode (closed).
• To end configuration do not press any buttons for 10 seconds.
5- BOOSTER HEATING SELECTION
(supplementary heating)
Units fitted with electric heaters can be enabled for the
“Booster Heating” function (supplementary heating)
This function permits heating using hot water and the electric
heaters at the same time.
To perform the configuration proceed as follows:
• Press and hold down the “
UP” and “DOWN” keys at the same
time for around 5 seconds.
• Press “
UP” button until “-5” is displayed.
• Press the “MODE” button to select the mode.
• Press the “
UP” or “DOWN” button to go from the “OFF” mode
(Booster Heating not enabled) to the “ON” mode (Booster
Heating enabled).
• To end configuration do not press any buttons for 10 seconds.