53
FAN ELECTRICAL DATA
(Single Point Standard Low-Sound AeroAcoustic™ Fans)
FAN ELECTRICAL DATA
(Single Point Optional Value Sound Fans)
LEGEND
NOTES:
1. Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed minimum and max-
imum limits. Maximum allowable phase imbalance is: voltage, 2%;
amps 10%.
2. All units/modules have single point primary power connection. (Each
unit/module requires its own power supply.) Main power must be sup-
plied from a field-supplied disconnect.
3. The unit control circuit power transformer (24 v, single-phase for all
voltages) is factory supplied.
4. Cooler heaters are wired into the main power circuit so they are always
operable as long as the disconnect is on, even if any safety device is
open, and the unit ON/OFF switch is in the OFF position.
UNIT
30RAP
UNIT VOLTAGE
V-Hz (3 Ph)
STANDARD CONDENSER
FANS
Quantity
FLA
(each)
010
208/230-60 1 6.0
380-60 1 3.9
460-60 1 2.9
575-60 1 2.4
015
208/230-60 1 6.0
380-60 1 3.9
460-60 1 2.9
575-60 1 2.4
018
208/230-60 2 6.0
380-60 2 3.9
460-60 2 2.9
575-60 2 2.4
020
208/230-60 2 6.0
380-60 2 3.9
460-60 2 2.9
575-60 2 2.4
025
208/230-60 2 6.0
380-60 2 3.9
460-60 2 2.9
575-60 2 2.4
030
208/230-60 2 6.0
380-60 2 3.9
460-60 2 2.9
575-60 2 2.4
035
208/230-60 3 6.0
380-60 3 3.9
460-60 3 2.9
575-60 3 2.4
040
208/230-60 3 6.0
380-60 3 3.9
460-60 3 2.9
575-60 3 2.4
045
208/230-60 3 6.0
380-60 3 3.9
460-60 3 2.9
575-60 3 2.4
050
208/230-60 3 6.0
380-60 3 3.9
460-60 3 2.9
575-60 3 2.4
055
208/230-60 4 6.0
380-60 4 3.9
460-60 4 2.9
575-60 4 2.4
060
208/230-60 4 6.0
380-60 4 3.9
460-60 4 2.9
575-60 4 2.4
070
208/230-60 5 6.0
380-60 5 3.9
460-60 5 2.9
575-60 5 2.4
080
208/230-60 6 6.0
380-60 6 3.9
460-60 6 2.9
575-60 6 2.4
090
208/230-60 6 6.0
380-60 6 3.9
460-60 6 2.9
575-60 6 2.4
UNIT
30RAP
UNIT VOLTAGE
V-Hz (3 Ph)
OPTIONAL CONDENSER
FAN S
Quantity
FLA
(each)
010
208/230-60 1 6.6
380-60 1 3.9
460-60 1 3.3
575-60 1 2.6
015
208/230-60 1 6.6
380-60 1 3.9
460-60 1 3.3
575-60 1 2.6
018
208/230-60 2 6.6
380-60 2 3.9
460-60 2 3.3
575-60 2 2.6
020
208/230-60 2 6.6
380-60 2 3.9
460-60 2 3.3
575-60 2 2.6
025
208/230-60 2 6.6
380-60 2 3.9
460-60 2 3.3
575-60 2 2.6
030
208/230-60 2 6.6
380-60 2 3.9
460-60 2 3.3
575-60 2 2.6
035
208/230-60 3 6.6
380-60 3 3.9
460-60 3 3.3
575-60 3 2.6
040
208/230-60 3 6.6
380-60 3 3.9
460-60 3 3.3
575-60 3 2.6
045
208/230-60 3 6.6
380-60 3 3.9
460-60 3 3.3
575-60 3 2.6
050
208/230-60 3 6.6
380-60 3 3.9
460-60 3 3.3
575-60 3 2.6
055
208/230-60 4 6.6
380-60 4 3.9
460-60 4 3.3
575-60 4 2.6
060
208/230-60 4 6.6
380-60 4 3.9
460-60 4 3.3
575-60 4 2.6
070
208/230-60 5 6.6
380-60 5 3.9
460-60 5 3.3
575-60 5 2.6
080
208/230-60 6 6.6
380-60 6 3.9
460-60 6 3.3
575-60 6 2.6
090
208/230-60 6 6.6
380-60 6 3.9
460-60 6 3.3
575-60 6 2.6
FLA — Full Load Amps