It is recommended to install units in a single row, arranged as shown in the example below, to avoid recycling hot air between
the units.
1500 mm
min.
1500 mm
min.

Plots
Antivibratiles
S
H
h
To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your distributor to assess the various installation options.
Anti-vibration
