22
For the high-pressure single and dual-pump motors of 30RBM/RBP 160-520 units (options 116R, 116S, 116V, 116W)
(2)
(3)
180 200 220 300 330 400 430 470 520
1 Nominaleciencyatfullloadandnominalvoltage % 87,5 87,5 87,5 87,5 89,9 89,9 89 89 89 89,6 89,6 89,6
1 Nominaleciencyat75%offullloadandnominalvoltage % 88,2 88,2 88,2 88,2 90,4 90,4 90 90 90 90,8 90,8 90,8
1 Nominaleciencyat50%offullloadandnominalvoltage % 87,5 87,5 87,5 87,5 89,6 89,6 89,7 89,7 89,7 90,8 90,8 90,8
2 Eciencylevel - IE3
3 Year of manufacture - This information varies depending on the manufacturer and model at the time of
incorporation.Pleaserefertothemotornameplates.
4 Manufacturer'snameandtrademark,commercialregistration
numberandmanufacturer'sheadoce
- Same as above
5 Product'smodelnumber - Same as above
6 Number of motor poles - 2 2 2 2 2 2 2 2 2 2 2 2
7-1 Nominal shaft power output at full load and nominal voltage (400 V) kW 3 3 3 3 4 4 5,5 5,5 5,5 7,5 7,5 7,5
7-2 Maximum input power (400 V)
(4)
kW 3,81 3,81 3,81 3,81 4,96 4,96 6,80 6,80 6,80 9,16 9,16 9,16
8 Rated input frequency Hz 50 50 50 50 50 50 50 50 50 50 50 50
9-1 Nominal voltage V 3 X 400
9-2
Maximum current drawn (400 V)
(5)
A 6,81 6,81 6,81 6,81 8,27 8,27 11,30 11,30 11,30 15,30 15,30 15,30
10 Nominal speed rps - rpm 48-2900
11 Productdisassembly,recyclingordisposalatendoflife - Disassemblyusingstandardtools.Disposalandrecyclingusinganappropriate
company.
12 Operatingconditionsforwhichthemotorisspecicallydesigned
I-Altitudesabovesealevel m < 1000
(6)
II-Ambientairtemperature °C < 40
III-Maximumoperatingtemperature °C Please refer to the operating conditions given in this manual or
inthespecicconditionsgivenintheCarrierselectionprograms.
V - Potentially explosive atmospheres - Non ATEX environment
(1) RequiredbyregulationNo.640/2009concerningtheapplicationofdirective2009/125/EContheeco-designrequirementsforelectricmotors.
(2) ItemnumberimposedbyregulationNo.640/2009,annexI2b.
(3) DescriptiongivenbyregulationNo.640/2009,annexI2b.
(4) Toobtainthemaximuminputpowerforaunitwithhydraulicmodule,addthemaximumunitinputpowerfromtheelectricaldatatabletothepumppowerinput.
(5) Toobtainthemaximumoperatingcurrentdrawforaunitwithhydraulicmodule,addthemaximumunitcurrentdrawfromtheelectricaldatatabletothepumpcurrentdraw.
(6) Above1000m,adegradationof3%foreach500mshouldbetakenintoconsideration.
Phi Max
30 41 44 215 0,89
37 50 54 260 0,89
Cp Compressor
INom Nominalcurrentdraw(A)atstandardisedEuroventequivalentconditions(seedenitionofconditionsundernominalunitcurrentdraw)
IMax Maximumoperatingcurrent(A)
LRA Locked rotor current (A)
CosphiMax @IMax
180 200 220 300 330 400 430 470 520
A 1 - - 2 - - - 3 - 3 - -
B 2 2 - 2 - 3 - - - - - -
A - 1 1 - 2 2 2 - 3 - 3 4
B - - 2 - 2 - 3 3 3 4 4 4
Cp Compressor
INom Nominalcurrentdraw(A)atstandardisedEuroventequivalentconditions(seedenitionofconditionsundernominalunitcurrentdraw)
IMax Maximumoperatingcurrent(A)
LRA Locked rotor current (A)
CosphiMax @IMax