Table 3 — 50VQP072-360 Electrical Data
LEGEND
NOTES:
1. HACR circuit breaker in U.S.A. only.
2. A voltage variation of ± 10% of nameplate rating is acceptable.
Phase imbalance shall not exceed 2%.
3. See WSHP Builder for electrical data for configurations not listed
above.
50VQP UNIT SIZE
VOLTAGE
(V-Ph-Hz)
COMPRESSOR (x2) BLOWER MOTOR
MIN CIRCUIT
AMPS
MAX FUSE/
HACR
RLA LRA QTY FLA HP
072
208/230-1-60 16.7 79.0 1 7.0 1 44.6 60
208/230-3-60 10.4 73.0 1 3.6 1 27.0 35
460-3-60 5.8 38.0 1 1.8 1 14.9 20
096
208/230-1-60
19.6 130.0 1 8.5 1
1
/
2
52.6 70
208/230-3-60 13.7 83.1 1 4.8 1
1
/
2
35.6 45
460-3-60 6.2 41.0 1 2.4 1
1
/
2
16.4 20
575-3-60 4.8 33.0 1 2.0 1
1
/
2
12.8 15
120
208/230-1-60 26.3 134.0 1 9.8 2 69.0 90
208/230-3-60 15.6 110.0 1 6.2 2 41.3 50
460-3-60 7.8 52.0 1 3.1 2 20.7 25
575-3-60 5.8 38.9 1 2.6 2 15.7 20
151
208/230-3-60 19.2 136.0 1 8.0 3 51.2 70
460-3-60 8.7 66.1 1 3.9 3 23.5 30
575-3-60 6.9 55.3 1 3.7 3 19.2 25
181
208/230-3-60 22.4 149.0 1 13.4 5 63.8 80
460-3-60 10.6 75.0 1 6.6 5 30.5 40
575-3-60 7.7 54.0 1
5.4 5 22.7 30
210
208/230-3-60 29.5 195.0 2 4.8 1
1
/
2
76.0 100
460-3-60 14.7 95.0 2 2.4 1
1
/
2
37.9 50
575-3-60 12.2 80.0 2 2.0 1
1
/
2
31.5 40
240
208/230-3-60 30.1 225.0 2 6.2 2 80.1 110
460-3-60 16.7 114.0 2 3.1 2 43.8 60
575-3-60 12.2 80.0 2 2.6 2 32.7 40
300
208/230-3-60 48.1 245.0 2 8.0 3 124.2 150
460-3-60 18.6 125.0 2 3.9 3 49.7 60
575-3-60 14.7 100.0 2 3.7 3 40.5 50
360
208/230-3-60 55.8 340.0 2 13.4 5 152.4 200
460-3-60 26.9 173.0 2 6.6 5 73.7 100
575-3-60 23.7 132.0 2 5.4 5 64.1 80
FLA Full Load Amps
HACR Heating, Air Conditioning, and Refrigeration
LRA Locked Rotor Amps
RLA Rated Load Amps