HEATING CYCLE ANALYSIS
COOLING CYCLE ANALYSIS
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =
FLOW RATE (gpm) x TEMP. DIFF. (DEG. F) x FLUID FACTOR* =
(Btu/hr)
SUPERHEAT = SUCTION TEMPERATURE – SATURATED SUCTION TEMPERATURE
=
(DEG F)
SUBCOOLING = SATURATED CONDENSING TEMPERATURE – LIQUID LINE TEMPERATURE
=
(DEG F)
*Use 500 for water, 485 for antifreeze.
SUCTION
COMPRESSOR
DISCHARGE
COAX
EXPANSION
VALVE
F
F
AIR
COIL
F
ft wg
WATER OUT
WATER IN
F
ft wg
LOOK UP PRESSURE DROP IN TABLE 12
TO DETERMINE FLOW RATE
F
LIQUID LINE
ft wg
F
SST
(SATURATED
SUCTION
TEMPERATURE)
a50-8453