ELECTRICAL DATA (CONT)
UNIT
NOMINAL
V-PH-HZ
VOLTAGE
RANGE
COMPRESSOR OFM IFM ELECTRIC HEAT POWER SUPPLY
MIN MAX RLA LRA MCC FLA FLA
NOMINAL
kW
FLA MCA MOCP
50EZ-A60---30-- 208/ 230-1-60 197 253 27.4 134 41.2 1.2 7.6
-/- -/- 43.1 60
3.8/5 18.1/20.8 65.7/69.1 70/70
5.4/7.2 25.9/30 75.4/80.6 80/90
7.5/10 36.1/41.7 88.2/95.2 90/100
11.3/15 54.2/62.5 110.8/121.2 125/125
15/20 72.2/83.3 133.3/147.2 150/150
50EZ-A60---50-- 208/ 230-3-60 197 253 18.4 110 24.9 1.2 7.6
-/- -/- 31.8 45
3.8/5 10.4/ 12 44.8/46.8 45/50
7.5/10 20.8/24.1 57.8/61.9 60/70
11.3/15 31.2/36.1 70.8/76.9 80/80
15/19.91 41.4/47.9 83.6/91.7 90/100
50EZ-A60---60-- 460-3-60 414 506 8 52 12.1 0.5 3.8
-/- -/- 14.3 20
3.8/5 6 21.8/21.8 25
7.5/10 12 29.3/29.3 30
11.3/15 18 36.8/36.8 40
15/20 24.1 44.4/ 44.4 45
See L egend and Notes below.