59SC5B: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
SPECIFICATIONS
The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because of furnace model size
capacity increments. None of the furnace model sizes can be used if the heating load is 12,000 BTUH or lower. Use Air Conditioning Contractors of
America (Manual J and S); American Society of Heating, Refrigerating, and Air-Conditioning Engineers; or other approved engineering method to
calculate heating load estimates and select the furnace. Excessive oversizing of the furnace may cause the furnace and/or vent to fail prematurely,
customer discomfort and/or vent freezing.
Failure to follow these guidelines is considered faulty installation and/or misapplication of the furnace; and resulting failure, damage, or repairs may
impact warranty coverage.
Furnace Model 026E14--10 040E14--10 040E17--12 060E14--12 060E17--14
Heating Capacity and Efficiency
Input (BTUh) 26,000 40,000 40,000 60,000 60,000
Output (BTUh) 25,000 39,000 39,000 58,000 58,000
Certified Temperature Rise Range ºF (ºC)
25 55
(14 31)
40 70
(22 39)
40 70
(22 39)
45 75
(25 42)
40 70
(22 39)
Airflow Capacity and Blower Data
Rated External Static
Pressure (in. w.c.)
Heating 0.10 0.10 0.10 0.12 0.12
Cooling 0.50 0.50 0.50 0.50 0.50
Airflow Delivery @ Rated
ESP (CFM)
Heating 605 695 650 930 1010
Cooling 895 950 1010 1120 1330
Cooling Capacity (tons) @
CFM/ton
400 CFM/ton 2 2 2.5 2.5 3.5
350 CFM/ton 2.50 2.50 3 3 4
DirectDrive Motor Type Electronically Commutated Motor (ECM)
DirectDrive Motor HP 1/3 1/2 1/2 1/2 3/4
Motor Full Load Amps 4.4 6.3 6.8 6.3 8.8
RPM Range 400 1200 600 2000 400 1200 600 2000 400 1200
Speed Selections 5 5 5 5 5
Blower Wheel Dia x Width in. 11 x 7 11 x 7 11 x 8 11 x 7 11 x 8
Air Filtration System Field Supplied Filter
Filter Used for Certified Watt Data 32553140*
Electrical Data
Input Voltage
VoltsHertz
Phase
115601
Operating
Voltage Range
MinMax 104127
Maximum Input Amps Amps 5.1 7.0 7.5 7.1 9.6
Unit Ampacity Amps 7.3 9.7 10.3 9.8 12.9
Minimum Wire Size AWG 14 14 14 14 14
Maximum Wire Length@
Minimum Wire Size
Feet 50 38 36 38 28
(M) (15.5) (11.7) (10.9) (11.5) (8.7)
Maximum Fuse/Ckt Bkr
(TimeDelay Type
Recommended)
Amps 15 15 15 15 15
Transfomer Capacity (24vac output) 40 VA
External Control Power
Available
Heating 27.9 VA
Cooling 34.6 VA
Controls
Gas Connection Size 1/2" NPT
Burners (Monoport) 2 2 2 3 3
Gas Valve (Redundant) Manufacturer White Rodgers
Minimum Inlet Gas pressure (in. wc) 4.50
Maximum Inlet Gas pressure (in. wc) 13.60
Manufactured (Mobile) Home Kit See Accessory Listing
Ignition Device Silicon Nitride
Heating Blower Control
(Heating OffDelay)
Adjustable: 90, 120, 150, 180 seconds
Cooling Blower Control
(Time Delay Relay)
90 seconds
Communication System none
Thermostat Connections Com 24V, R, W, G, Y
Accessory Connections EAC (115vac); HUM (24vac); 1stg AC (via Y)