Table 27 Configuring Temperature Reset
Table 28 Return Water Reset
MODE
KEYPAD
ENTRY
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
CONFIGURATION
DISP TEST ON/OFF TEST DISPLAY LEDs
UNIT TYPE X UNIT TYPE
OPT1 FLUD X COOLER FLUID
OPT2 CTRL X CONTROL METHOD
RSET CRST X COOLING RESET TYPE 0 = No Reset
1 = 4 to 20 mA Input (EMM required)
(Connect to EMM J6-2,5)
2 = Outdoor-Air Temperature
(Connect to TB5-7,8)
3= ReturnFluid
4 = Space Temperature
(Connect to TB5-5,6)
CRT1 XXX.X F NO COOL RESET TEMP
Default: 125 F (51.7 C)
Range: to125 F
Set to 4.0 for CRST= 1
No Cool Reset T for CRST=3
CRT2 XXX.X F FULL COOL RESET TEMP
Default: F (–17.8 C)
Range: to 125 F
Set to 20.0 for CRST=1
Full Cool Reset T for CRST=3
DGRC XX.X F DEGREES COOL RESET
Default: F (0° C)
Range: –30 to 30 F (–16.7 to 16.7 C)
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
RSET
CRST 3
COOLING RESET
TYPE
0 = no reset
1=4to20mAinput
2 = Outdoor air temp
3=ReturnFluid
4 = Space Temperature
CRT1
10.0 F
(5.5 C)
NO COOL RESET
TEMP
Default: 125 F (51.7 C)
Range: to 125 F
CRT2
2.0 F
(1.1 C)
FULL COOL
RESET TEMP
Default: F (–17.8 C)
Range: to 125 F
DGRC
5.0 F
(2.8 C)
DEGREES COOL
RESET
Default: 0°F (0° C)
Range: –30 to 30 F (–16.7 to 16.7 C)
ENTER ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
LEGEND
Fig. 14 Cooling Return Water No Reset
EWT Entering Water (Fluid) Temperature
LWT Leaving Water (Fluid) Temperature
LEGEND
LWT Leaving Water (Fluid) Temperature
Fig. 15 Outdoor-Air Temperature Reset