EasyManua.ls Logo

Carrier ComfortLink 30HXA - TESTMODE: Maintenance Display

Carrier ComfortLink 30HXA
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
124
APPENDIX G (cont)
TESTMODE: Maintenance Display
VERSIONS: Maintenance Display
DESCRIPTION STATUS UNITS POINT
Service Test Mode On/Off MAN_CTRL
Manual Control Override On/Off FAC_CTRL
Compressor A1 Relay On/Off S_A1_RLY
Compressor A2 Relay On/Off S_A2_RLY
Compressor B1 Relay On/Off S_B1_RLY
Compressor B2 Relay On/Off S_B2_RLY
Loader A1 Relay On/Off S_LDR_A1
Loader A2 Relay On/Off S_LDR_A2
Loader B1 Relay On/Off S_LDR_B1
Loader B2 Relay On/Off S_LDR_B2
Oil Solenoid A1 On/Off S_OSL_A1
Oil Solenoid A2 On/Off S_OSL_A2
Oil Solenoid B1 On/Off S_OSL_B1
Oil Solenoid B2 On/Off S_OSL_B2
Motor Coolng A1 Solenoid On/Off S_MCS_A1
Motor Coolng A2 Solenoid On/Off S_MCS_A2
Motor Coolng B1 Solenoid On/Off S_MCS_B1
Motor Coolng B2 Solenoid On/Off S_MCS_B2
FAN 1 Relay On/Off S_FAN_1
FAN 2 Relay On/Off S_FAN_2
FAN 3 Relay On/Off S_FAN_3
FAN 4 Relay On/Off S_FAN_4
Oil Heater On/Off S_OHTR_A
Oil Heater On/Off S_OHTR_B
Oil Pump On/Off S_OPMP_A
Oil Pump On/Off S_OPMP_B
Cooler Pump Relay On/Off S_CL_PMP
Condenser Pump Relay On/Off S_CN_PMP
Minimum Load Valve On/Off S_MLV
Cooler Heater On/Off S_CHTR
Remote Alarm Relay On/Off S_ALRM
EXV % OPEN 0-100 % S_EXV_A
EXV % OPEN 0-100 % S_EXV_B
Var Head Press % 0-100 % S_VHPA
Var Head Press % 0-100 % S_VHPB
Liq. Line Solenoid Valve Open/Close S_LLSV
DESCRIPTION VERSION STATUS
MBB CESR131344- nn-nn
EXV CESR131172- nn-nn
EMM CESR131174- nn-nn
SCB CESR131226- nn-nn
TI CCP 1 100233-1R3- nn-nn
TI CCP 2 100233-1R3- nn-nn
NAVIGATOR CESR130227- nn-nn

Table of Contents