Table 12 Configuration Mode and Sub-Mode Directory (cont)
SUB-
MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
RSET CRST X COOLING RESET TYPE Default: No Reset
No Reset
4 to 20 mA Input
Outdoor Air Temperature
Return Fluid
Space Temperature
CRT1 XXX.X °F NO COOL RESET TEMP Default: 125 F
Range: 0° to 125 F
For return fluid reset use cooler ∆T
CRT2 XXX.X °F FULL COOL RESET TEMP Default: 0° F
Range: 0° to 125 F
For return fluid reset use cooler ∆T
DGRC XX.X ∆F DEGREES COOL RESET Default: 0° F
Range: –30 to 30 F
HRST X HEATING RESET TYPE Default: No Reset
No Reset
4 to 20 mA Input
Outdoor Air Temperature
Return Fluid
Space Temperature
HRT1 XXX.X °F NO HEAT RESET TEMP Default: 0° F
Range: 0° to 125 F
HRT2 XXX.X °F FULL HEAT RESET TEMP Default: 125 F
Range: 0° to 125 F
DGRH XX.X ∆F DEGREES HEAT RESET Default: 0° F
Range: –30 to 30 F
DMDC X DEMAND LIMIT SELECT Default: None
None
Switch
4 to 20 mA Input
CCN Loadshed
DM20 XXX % DEMAND LIMIT AT 20 mA Default: 100%
Range: 0 to 100%
SHNM XXX LOADSHED GROUP NUMBER Default: 0
Range: 0 to 99
SHDL XXX % LOADSHED DEMAND DELTA Default: 0%
Range: 0 to 60%
SHTM XXX MAXIMUM LOADSHED TIME Default: 60 Minutes
Range: 0 to 120 Minutes
DLS1 XXX % DEMAND LIMIT SWITCH 1 Default: 80%
Range: 0 to 100%
DLS2 XXX % DEMAND LIMIT SWITCH 2 Default: 50%
Range: 0 to 100%
LLEN ENBL/DSBL LEAD/LAG CHILLER ENABLE Default: Disable
MSSL SLVE/MAST MASTER/SLAVE SELECT Default: Master
SLVA XXX SLAVE ADDRESS Default: 0
Range: 0 to 239
LLBL X LEAD/LAG BALANCE SELECT Default: Master Leads
Master Leads
Slave Leads
Automatic
LLBD XXX LEAD/LAG BALANCE DELTA Default: 168 hours
Range: 40 to 400 hours
LLDY XXX LAG START DELAY Default: 5 minutes
Range: 0 to 30 minutes
PARA YES/NO PARALLEL CONFIGURATION Default: No (Series Flow)
ENTER