Table 17 Inputs Mode and Sub-Mode Directory
SUB-MODE
KEYPAD
ENTRY
ITEM DISPLAY
ITEM
EXPANSION
COMMENT
GEN.I STST STRT/STOP START/STOP SWITCH
FLOW ON/OFF COOLER FLOW SWITCH
CND.F ON/OFF CONDENSER FLOW SWITCH
DLS1 ON/OFF DEMAND LIMIT SWITCH 1
DLS2 ON/OFF DEMAND LIMIT SWITCH 2
ICED ON/OFF ICE DONE
DUAL ON/OFF DUAL SETPOINT SWITCH
CRCT FKA1 ON/OFF COMPRESSOR A1 FEEDBACK
FKA2 ON/OFF COMPRESSOR A2 FEEDBACK
OIL.A OPEN/CLSE OIL LEVEL SWITCH
A1.CR XXX AMPS COMP A1 RUNNING CURRENT
A2.CR XXX AMPS COMP A2 RUNNING CURRENT
FKB1 ON/OFF COMPRESSOR B1 FEEDBACK
FKB2 ON/OFF COMPRESSOR B2 FEEDBACK
OIL.B OPEN/CLSE OIL LEVEL SWITCH
B1.CR XXX AMPS COMP B1 RUNNING CURRENT
B2.CR XXX AMPS COMP B2 RUNNING CURRENT
4-20 DMND XX.X MA 4-20 MA DEMAND SIGNAL
RSET XX.X MA 4-20 MA RESET SIGNAL
CSP XX.X MA 4-20 MA COOLING SETPOINT
HSP XX.X MA 4-20 MA HEATING SETPOINT
ENTER
ENTER
ENTER