ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
12
1 Teconomizer temperature < Room temperature - (Cool differential band / 2)
2 Room Temperature > Setpoint temperature
Economizer will stop when the following condition is satisfied:
1 Room Temperature < Setpoint temperature - (Cool differential band / 2)
Indication for the Economizer operation:
When Economizer is active, the Cool symbol will appear on display and the Fan
symbol will flash.