ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
20
3 Change the Present Value field (shown below) to the desired BACnet Device Instance Number.
4 Click Accept.
In an Analog Network Output microblock
To change the BACnet Device Instance Number from 16075 to 16113, the microblock’s address would be:
bacnet://16075/AV:42/present_value, or
bacnet://16075/BACnetDeviceInstanceNumber
Subsequent reads/writes of this value will need to be done with the new device instance:
bacnet://16113/AV:42/present_value, or
bacnet://16113/BACnetDeviceInstanceNumber