ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
23
Wiring terminals and DIP switches
11
T1
For outputs 11-16, see
Wiring and DIP
switch/jumper settings
For T1,0 inputs:
Dry contact, 10 Vdc input, or
50 kOhm thermistor
See Technician Setting P8.
12
0
13
IN1
For IN1,0 inputs:
Dry contact, 10 Vdc input, or
50 kOhm thermistor
See Technician Setting P9.
14
0
15
AO1
See options.
16
AO2
Power supply:
110-230 Vac line voltage
CAUTION Do not connect
line voltage to a
thermostat that does not
show the following
symbol:
R*
B (-)
MS/TP Communication
(RS485)
BACnet
C*
A (+)
Terminals
DIP Switch SW4.1 - End of line resistor (120Ω)
First and last units in communication line must be configured
with 120Ω End of line resistor.
Always OFF
See Wiring and DIP switch settings (page 27).