ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
29
Wiring and DIP switch configurations 9 to 12 AC systems
Outputs
Config. 9:
HC22
1 Speed fan,
Economizer
Config. 10:
HP32
1 Speed fan,
Economizer
Config. 11: HC32
1 Speed fan, Humidifier,
Dehum/Reheat for
Dehumidification
Config. 12: HP42
1 Speed fan,
Humidifier,
Dehum/Reheat for
Dehumidification
11
Heat element 2
(2nd stage heat)
Heat element
(3rd stage heat)
Heat element 3
(3rd stage heat)
Heat element 2
(4th stage heat)
12
Economizer
Economizer
Heat element 2
(2nd stage heat)
Heat element 1
(3rd stage heat)
13
Fan (1 speed)
Fan (1 speed)
Fan (1 speed)
Fan (1 speed)
14
Compressor 2
(3)
Compressor 2
(3)
Compressor 2
(3)
Compressor 2
(3)
15
Compressor 1
(3)
Compressor 1
(3)
Compressor 1
(3)
Compressor 1
(3)
16
Heat element 1
(1st stage heat)
Heat pump
(2)
Heat element 1
(1st stage heat)
Heat pump
(2)
AO1
X
X
Humidifier
Humidifier
AO2
X
X
Dehumidifier
(4)
(option - See SW2.3)
Dehumidifier
(4)
(option - See SW2.3)
SW1
SW2
(1)
SW1.1, SW1.2 Fan speeds:
2 speeds (Low and High):
3 speeds (Low, Med., and High):
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 = HP (Heat pump):
HC (Not Heat pump):
ON Heat pump active in cool
ON Electrical heater
OFF Heat pump active in heat
OFF Oil/Gas heater (no fan)
(3)
SW1.5 = Compressor delay:
ON Disable compressor delay, OFF Enable compressor delay
(4)
SW2.3 = Dehumidification:
ON Use dehumidifier, OFF Use reheat for dehum.
(5)
SW2.6 = Terminal 12:
ON Economizer, OFF Terminal not in use (1 Speed)
Important: Economizer will not work in 3 fan speeds configuration
See drawing for DIP switch and jumper locations.
Fan on/off: 110-230 Vac, 2.5A max.
Humidifier, Dehumidifier: 0-10 Vdc, 0.5 mA Not isolated
Control Heat elements, Heat pump, Compressors, Economizer: 110-230 Vac, 0.3A max.