ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential CARRIER CORPORATION ©2020
Installation and Operation Guide All rights reserved
31
Wiring and DIP switch configurations 17 to 20 – AC systems
(1)
,
Humidifier, Dehumidifier
(1)
,
Humidifier, Reheat for
Dehumidification
Fan VFS, Humidifier,
Reheat for
Dehumidification
Fan high
Fan high
X
X
Fan medium
(or Economizer
(5)
)
Fan medium
(or Economizer
(5)
)
Economizer
(5)
(option – SW2.6 ON)
Economizer
(5)
(option – SW2.6 ON)
Fan low
Fan low
X
X
Compressor 2
(3)
Heat element
(2nd stage heat)
Compressor 2
(3)
Heat element
(2nd stage heat)
Compressor 1
(3)
Compressor
(3)
Compressor 1
(3)
Compressor
(3)
Heat pump
(2)
Heat pump
(2)
Heat pump
(2)
Heat pump
(2)
Humidifier
Humidifier
Humidifier
Humidifier
Dehumidifier
X
Fan VFS
Fan VFS
(1)
SW1.1, SW1.2 – Fan speeds:
2 speeds (Low and High):
3 speeds (Low, Med., and High):
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 – HP (Heat pump):
HC (not heat pump):
ON = Heat pump active in cool, OFF = Heat pump active in heat
ON = Electrical heater, OFF = Oil/Gas heater (no fan)
(3)
SW1.5 – Compressor delay:
ON = Disable, OFF = Enable
(4)
SW2.3 – Dehumidification:
ON = Use dehumidifier
OFF = Use reheat for dehumidification
(5)
SW2.6 – Terminal 12 operation:
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
See drawing in Wiring terminals and DIP switches (page 23) for DIP switch locations.
Fan on/off: 110-230 Vac, 2.5A max.
Fan VFS, Humidifier, Dehumidifier: 0-10 Vdc, 0.5 mA Not isolated
Control – Heat elements, Heat pump, Compressors, Economizer: 110-230 Vac, 0.3A max.