Technician Settings P4 to P7
P4 – Enable/Disable the option to lock the [Fan] button
“01” [Fan] button can be locked
“00” [Fan] button cannot be locked
Note: When enabled, press and hold the [Mode] buttons for 7
seconds to unlock or relock the buttons.
P5 – Enable/Disable the option to lock the [Mode] button
“01” [Mode] button can be locked
“00” [Mode] button cannot be locked
Note: When enabled, press and hold the [Mode] for 7 seconds to
unlock or relock the buttons.
P6 – Enable/Disable the option to lock the [On/Off] button
“01” [On/Off] button can be locked
“00” [On/Off] button cannot be locked
Note: When enabled, press and hold the [Mode] for 7 seconds to
unlock or relock the buttons.
P7 – Enable/Disable the option to lock the
▲or ▼button
(SET)
“01” or ▼button can be locked
“00” or ▼button cannot be locked
Note: When enabled, press and hold the [Mode] for 7 seconds to
unlock or relock the buttons.
P4-P7 Note:
When the option to lock one or more buttons is enabled, these buttons will be automatically locked when leaving technician
settings and returning to normal display. In normal display, press and hold the [Mode] button for 7 seconds to unlock/relock
these buttons.