EasyManua.ls Logo

Carrier ComfortVu TB-24-HM - Page 26

Carrier ComfortVu TB-24-HM
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
12
13
14
15
16
Config. 5:
HC21
2/3 Speeds fan
Fan medium
(or Economizer )
Fan high
Fan low
Heat element 2
(2
nd
stage heat)
Compressor
Heat element 1
(1
st
stage heat)
Config. 6:
HP11
Fan VFS
Heat pump
Compressor
Fan VFS
Config. 7:
HC11
Fan VFS
Heat element
Compressor
Fan VFS
Economizer
(option – SW1.6 ON)
X
X
X
X
SW3
SW1
87654321
654321
87654321
654321
87654321
654321
JP3
JP2
3
Jumpers
JP2, JP3
for analog
outputs
1
3 1
JP3
JP2
3 1
3 1
JP3
JP2
3 1
3 1
- 26 -
Wiring and DIP switch/jumper configurations – AC
systems
Outputs
See drawing on page 21 for DIP switch and jumper locations.
Fan VFS: 0-10 Vdc, 0.5 mA Not isolated
Control – Fan on/off, Heat elements, Heat pump, Compressors, Economizer: 24 Vac, 0.5A max
(1)
SW3.1, SW3.2 – Fan speeds: 2 speeds (Low and High): SW3.1 = OFF, SW3.2 = ON
3 speeds (Low, Med., and High): SW3.1 = OFF, SW3.2 = OFF
(2)
SW3.4 – HP (Heat pump): ON = Heat pump active in cool, OFF = Heat pump active in heat
HC (not heat pump): ON = Electrical heater, OFF = Oil/Gas heater (no fan)
(3)
SW3.5 – Compressor delay: ON = Disable, OFF = Enable
(5)
SW1.6 – Terminal 12 operation: ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (2 speeds)
Important: Economizer will not work in 3 fan speeds configuration.
(5)
(5)
Economizer
(option – SW1.6 ON)
(5)
(2) (2)