Enter Technician Settings mode:
1. Adjust the setpoint temperature to 10ºC or 50ºF.
2. Press and hold the [C/F] button for 10 seconds to enter Technician Settings mode. “P01” will appear on display.
View objects and make adjustments:
Use the [Mode] button to step forward between different settings.
Use the [Fan] button to step backward between different settings.
Press the [On/Off] button to exit Technician Settings and return to normal display.
If no button is pressed for 60 seconds, the thermostat will automatically exit Technician Settings and return to normal display.
Use the [+] and [-] buttons to make adjustments when required.
P01 – Offset for temperature readings calibration
Range: -6…+6°C / -9…+9°F.
Default: 0°C / 0°F.
P02 – Setpoint limit for cooling
Range: 5…35°C / 41…95°F.
Default: 10°C / 50°F.
P03 – Setpoint limit for heating
Range: 5…35°C / 41…95°F.
Default: 30°C / 86°F.
Setpoint limit for cooling
(°F)(°C)
Setpoint limit for heating
(°F)(°C)
Offset for temperature calibration
(°F)(°C)
Note: The offset will influence both internal
or external sensors.
Note: The thermostat will stop cooling regardless of
the user’s setpoint
Note: The thermostat will stop heating regardless of
the user’s setpoint
- 40 -
Technician Settings
P04 – Enable/Disable the option to lock the [Fan] button
“LF” + “ ” [Fan] button can be locked
“LF” only [Fan] button cannot be locked
[Fan]
Can
be locked
[Fan]
Cannot
be locked
Note: When enabled, press and hold both [-] and [Fan] buttons
for 7 seconds to actually lock the buttons.