P19 – PIR (Motion sensor) polarity
“00” - Normally open
“01” - Normally closed
PIR
Normally open
PIR
Normally closed
P25 – Economy setpoint for cooling
Range: 5…35°C / 41…95°F.
Default: 30°C / 86°F.
EC setpoint in cooling
(°F)(°C)
- 44 -
Technician Settings (cont.)
P26 – Economy setpoint for heating
Range: 5…35°C / 41…95°F.
Default: 10°C / 50°F.
EC setpoint in heating
P28 – Off-delay time between heating stages
Range: 0….600 seconds
Default: 1 second
Off delay
heating stages
P27 – On-delay time between heating stages
Range: 0….600 seconds
Default: 5 seconds
On delay
heating stages
P29 – LCD Backlight ON or OFF
“00” - LCD Backlight ON
“01” - LCD Backlight OFF
Backlight
ON
Backlight
OFF
(°F)(°C)