Technician Settings (cont.)
P187 – Display or hide humidity reading
“00” - Do not display humidity reading
“01” - Display humidity reading
P122 – Cool Proportional output threshold time (seconds) (FC Only!)
Range: 0...100 seconds
Default: 60 seconds
P123 – Heat Proportional output threshold time (seconds) (FC Only!)
Range: 0...100 seconds
Default: 60 seconds
P188 – Room temperature limit for disabling dehumidification in
unoccupied mode
Range: 10...30ºC / 50...85ºF
Default: 18ºC / 64ºF
Cool proportional
cooling threshold
Heat proportional
cooling threshold
Display or hide
humidity readings
Temp. for disabling
dehum. In unocc mode
P160 – Minimum compressor ON time
Range: 0...20 minutes
Default: 2 minutes
Min. compressor
ON time
P161 – Minimum compressor OFF time
Range: 0...20 minutes
Default: 13 minutes
Min. Compressor
OFF time
(°F)(°C)
P170 – Economizer low limit temperature
Range: 9...27ºC / 48...80ºF
Default: 17ºC / 63ºF
Economizer low
limit temperature
(°F)(°C)