Configuring the system
33CONNECTSTAT43 ©2022 Carrier.
Installation Guide All rights reserved.
20
Parameter Name/Description
Default and Range
MSTP MAC ADDRESS Unique identifier for this thermostat on the MSTP network
D:
R:
1
1 TO 127
BACNET UTC OFFSET Offset applied to UTC time
D:
R:
5 hrs / 0 min
-13 to 13 hrs / 0 min
DEVICE ID This is a unique identifier for this thermostat. The default is the Carrier
BACnet identifier (16) and the last 4 digits of the thermostat serial number.
D:
R:
16xxxx
1 TO 4194302
DEVICE OBJECT NAME Assign a unique alpha-numeric string. The default is the Carrier
BACnet identifier (16) and the last 4 digits of the thermostat serial number. This
parameter is limited to a maximum of 16 characters.
16xxxx
DEVICE LOCATION (Optional) Use to provide details about thermostat location.
(Location)
DEVICE DESCRIPTION (Optional) Use to provide additional details about this
thermostat.
(Description)
BACNET BMS OCC Use to enable or disable BACnet occupancy control.
NOTE Occupancy is determined by 1 of 3 methods. You cannot have BACNET BMS OCC
with both PROGRAMMABLE MODE and REMOTE SENSOR set to OCCUPANCY. Setting
BACNET BMS OCC to YES forces PROG OR NON-PROG to NON-PROG and switches
REMOTE SENSOR to NONE if set to OCCUPANCY.
D:
R:
NO
YES
NO
BACNET CONFIG WRITE If YES, allows BACnet to write to GATED_WRITE points. See
Appendix BACnet Points List.
D:
R:
NO
NO
YES
NET GP OUT TIMEOUT Used to timeout Network General Purpose Outputs.
NOTES
Sets the maximum time to lapse between writes to the present_value property of the
output object before it returns to INACTIVE.
Accessible only if Y3, W2, or O/B output is available as a GP OUTPUT.
D:
R:
2 MIN
2 MIN
20 MIN
1 HR
UNLIMITED
NET GP Y3 MODE Controls the Y3 output over the BACnet network.
DISABLED sets the Present_Value of the BACnet object to INACTIVE and READ_ONLY
and the corresponding output relay will be in a de-energized state
Selecting ENERGIZE ACTIVE allows BACnet writes and energizes the output relay
when the Present_Value is ACTIVE.
Selecting ENERGIZE INACTIVE allows BACnet writes and will energize the output relay
when the Present_Value is INACTIVE.
D:
R:
DISABLED
DISABLED
ENERGIZED ACTIVE
ENERGIZED INACTIVE
NET GP W2 MODE Controls the W2 output over the BACnet network.
DISABLED sets the Present_Value of the BACnet object to inactive and read-only and
the corresponding output relay will be in a de-energized state.
ENERGIZED ACTIVE allows BACnet writes and energizes the output relay when the
Present_Value is ACTIVE.
ENERGIZED INACTIVE allows BACnet writes and energizes the output relay when the
Present_Value is INACTIVE.
D:
R:
DISABLED
DISABLED
ENERGIZED ACTIVE
ENERGIZED INACTIVE