Configuring the system
33CONNECTSTAT43 ©2022 Carrier.
Installation Guide All rights reserved.
20
Parameter Name/Description
MSTP MAC ADDRESS — Unique identifier for this thermostat on the MSTP network
BACNET UTC OFFSET — Offset applied to UTC time
5 hrs / 0 min
-13 to 13 hrs / 0 min
DEVICE ID — This is a unique identifier for this thermostat. The default is the Carrier
BACnet identifier (16) and the last 4 digits of the thermostat serial number.
DEVICE OBJECT NAME — Assign a unique alpha-numeric string. The default is the Carrier
BACnet identifier (16) and the last 4 digits of the thermostat serial number. This
parameter is limited to a maximum of 16 characters.
DEVICE LOCATION — (Optional) Use to provide details about thermostat location.
DEVICE DESCRIPTION — (Optional) Use to provide additional details about this
thermostat.
BACNET BMS OCC — Use to enable or disable BACnet occupancy control.
NOTE Occupancy is determined by 1 of 3 methods. You cannot have BACNET BMS OCC
with both PROGRAMMABLE MODE and REMOTE SENSOR set to OCCUPANCY. Setting
BACNET BMS OCC to YES forces PROG OR NON-PROG to NON-PROG and switches
REMOTE SENSOR to NONE if set to OCCUPANCY.
BACNET CONFIG WRITE — If YES, allows BACnet to write to GATED_WRITE points. See
Appendix BACnet Points List.
NET GP OUT TIMEOUT — Used to timeout Network General Purpose Outputs.
NOTES
• Sets the maximum time to lapse between writes to the present_value property of the
output object before it returns to INACTIVE.
• Accessible only if Y3, W2, or O/B output is available as a GP OUTPUT.
2 MIN
2 MIN
20 MIN
1 HR
UNLIMITED
NET GP Y3 MODE — Controls the Y3 output over the BACnet network.
• DISABLED sets the Present_Value of the BACnet object to INACTIVE and READ_ONLY
and the corresponding output relay will be in a de-energized state
• Selecting ENERGIZE ACTIVE allows BACnet writes and energizes the output relay
when the Present_Value is ACTIVE.
• Selecting ENERGIZE INACTIVE allows BACnet writes and will energize the output relay
when the Present_Value is INACTIVE.
DISABLED
DISABLED
ENERGIZED ACTIVE
ENERGIZED INACTIVE
NET GP W2 MODE — Controls the W2 output over the BACnet network.
• DISABLED sets the Present_Value of the BACnet object to inactive and read-only and
the corresponding output relay will be in a de-energized state.
• ENERGIZED ACTIVE allows BACnet writes and energizes the output relay when the
Present_Value is ACTIVE.
• ENERGIZED INACTIVE allows BACnet writes and energizes the output relay when the
Present_Value is INACTIVE.
DISABLED
DISABLED
ENERGIZED ACTIVE
ENERGIZED INACTIVE