Using installer settings
Carrier Connect™ Wi-Fi Thermostat 33CONNECTSTAT43FX CARRIER CORPORATION ©2021
Installation Guide All rights reserved
34
Setting
Default/Range
TIME BETWEEN FUEL TYPES (ELECTRIC TO GAS)Sets a minimum amount of time that
the system runs on compressor heat before transitioning to the furnace.
Range - The minimum number of minutes the compressor is energized to satisfy a
heating demand before transitioning to gas heat.
NOTES
This selection is only available if the HEATING EQUIPMENT is set to GAS and the
COMPRESSOR is set to HP.
The minimum number of minutes the compressor runs in heating before staging up
to gas heat is the larger of this setting and the STAGE DELAY setting.
D:
R:
15 minutes
10, 15, 20, 25 minutes
CYCLES PER HOURSets a maximum number of equipment cycles per hour. Based on
selecting 2, 4, 6 or 8 cycles per hour, this timer is set to 30, 15, 10 or 8 minutes. This
time must elapse from the start of one cycle before another cycle can start.
The Range - The maximum number of times the equipment can turn on per hour.
NOTE When the equipment is off and the user changes the setpoint to create a heating
or cooling demand, the cycles per hour requirement is ignored to provide a timely
response to the user’s request. The cycles per hour limitation become active again when
the Y1, Y2, W1 or W2 outputs transition from ON to OFF.
D:
R:
4
2, 4, 6, or 8
MAX HEAT SETPOINTSets a maximum heating setpoint. This is the maximum heat
setpoint value that can be used in the program schedule or when the user adjusts the
setpoint to temporarily override the program schedule.
NOTE This setting is not available if HEATING EQUIPMENT is set to NONE. (HEAT EQUIP =
ELEC and HEAT STAGES = 0)
D:
R:
88°F
50° 88°F
(1°F increments)
MIN COOL SETPOINTSets a minimum cooling setpoint that can be used in the program
schedule or when the user adjusts the setpoint to temporarily override the program
schedule.
NOTE This setting is not available if the COMPRESSOR is set to NONE.
D:
R:
52°F
52 90 °F
(1°F increments)