30
Combustion
Air
Exhaust
12
(304.8mm)
Min. Grade or
Snow Level
36” Min
2” (50.8mm) Max
36”Min
OR
(914.4mm)
(914. 4mm )
A07718
Fig. 26 -- Concentric Vent and Combustion--Air
Roof Termination
“A”
Vent
Dimension “A” is touching or 2 (50.8mm) maximum s eparation.
2 5 -- 2 2 -- 0 2 d
Vent
Combustion Air
1
(25.4mm)
Maximum
Exhaust
A07695
Fig. 27 -- Concentric Vent and Combustion Air
Sidewall Termination
12
(304.8mm) Min.
Grade or Snow Level
8
(457.2mm) Min.
20
(6.1m) Max.
“A”
“A”
Exhaust
Inlet
Dimension “A” is touching or 2 (50.8mm) maximum separation.
18
(457.2mm) Min. for Cold Climates
[Sustained 0
°
F(- 17
°
C) and below for
24 hours or more consecutive hours]
8
Min.
A07696
Fig. 28 -- Sidewall Inlet Vent and Exhaust--Air Termination
Exhaust
8
(203.2mm) Min.
Inlet
“A”
“A”
Dimension “A” is touching or 2 (50.8mm) maximum separation.
12
(457.2mm)
Min. Grade or
Snow Level
18
(457.2mm) Min. for Cold Climates
[Sustained 0
°
F(- 17
°
C) and below for
24 hours or more consecutive hours]
8
(203.2mm) Min.
20
(6.1m) Max.
A07697
Fig. 29 -- Sidewall Inlet Vent and Exhaust--Air Termination
with Exterior Risers
12
(304.8mm)
Min. Grade or
Snow Level
Exhaust
8
(203.2mm) Min.
20
(6.1m) Max.
25--22--43
Inlet
18
(457.2mm) Min. for Cold Climates
[Sustained 0
°
F(- 17
°
C) and below for
24 hours or more consecutive hours]
A07698
Fig. 30 -- Rooftop Inlet Vent and Exhaust--Air Termination