Table 19 Service Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
3 Options Configuration 2 (cont)
Ramp Load Select
x
0 = Disabled, 1 = Enabled (Default)
See page 8
Clock Control Select
x
0 = No clock control (Default)
1 = Local clock control
65 = CCN Clock Control
Ice Configuration Select
x
0 = Disabled (Default)
1 = Clock Control
2 = Demand Limit Control
OAT Sensor Select
x
0 = Disabled, 1 = Enabled
Default: 0
Remote Alarm Select
x
0 = Disabled, 1 = Enabled
Default: 0
Alarm Reset Select
x
0 = Not selected, 1 = Selected
(Default, allows use of LOR
switch to reset alarms)
Close Control Select
x
0 = Disabled, 1 = Enabled
Default: 0. See page 7
Deadband Multiplier
x.x
Default: 1.0
Current Unbalance Alarm
x
Alarm at 10% imbalance; 0 = Disabled, 1 = Enabled
Default: 1
Voltage Unbalance Alarm
x
Alarm at 3% imbalance; 0 = Disabled, 1 = Enabled
Default: 1
4 Reset Configuration Table
COOLING RESET TYPE
1
See Demand Limit section, page 39
Degrees Reset at 20 mA
xx.x dF
Default: 0
COOLING RESET TYPE
2
Remote temp=No Reset
xx.x dF
Default: 20
Remote temp=Full Reset
xx.x dF
Default: 125
Degrees Reset
xx.x dF
Default: 0
COOLING RESET TYPE
3
CHW Delta T=No Reset
xx.x dF
Default: 15
CHW Delta T=Full Reset
xx.x dF
Default: 0
Degrees Reset
xx.x dF
Default: 0
COOLING RESET
Select/Enable Reset Type
x
0 = No Reset (Default),1=4-20 mA Reset,
2 = External Reset, 3 = Return Fluid Reset
HEATING RESET TYPE
1
CURRENTLY NOT SUPPORTED
Degrees Reset at 20 mA
xx.x dF
Default: 0
HEATING RESET TYPE
2
CURRENTLY NOT SUPPORTED
Remote temp=No Reset
xx.x dF
Default: 125
Remote temp=Full Reset
xx.x dF
Default: 20
Degrees Reset
xx.x dF
Default: 0
HEATING RESET TYPE
3
CURRENTLY NOT SUPPORTED
HTW Delta T=No Reset
xx.x dF
Default: 15
HTW Delta T=Full Reset
xx.x dF
Default: 0
Degrees Reset
xx.x dF
Default: 0
HEATING RESET
Select/Enable Reset Type
x
0 = No Reset (Default), 1 = 4-20 mA reset,
2 = External reset, 3 = Return Fluid reset
DEMAND LIMIT See Demand Limit section, page 39
Demand Limit at 20 mA
xxx.x%
Enter 0-100, Default: 0%
32