5
Table 2 -- Menu Structure
a
(cont)
Menu Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
Notes
SETPOINTS MAT SET 53_F 38 to 65_F;
increment by 1
Setpoi nt determines where the economizer will modulate the OA damper
to maintain the mixed air temperature.
LOW T LOCK 32_F ---45 to 80_F;
increment by 1
Setpoi nt determines outdoor temperature when the mechanical cooling
canno t be turned on. Commo nly referred to as the Compre sso r locko ut .
DRYBLB SET 63_F 48 to 80_F;
increment by 1
Setpoi nt determines where the economizer will assume outdoor air
temperature is good for free cooling; e.g.: at 63_F unit will economize at
62_F and below and not economize at 64_F and above. There is a
2_F deadband.
ENTH CURVE ES3 ES1, ES2, ES3, ES4, or
ES5
Enthalp y boundary “curve s” for econo m izi ng using si ng le enthalpy.
DCV SET 1100ppm 500 to 2000 ppm;
increment by 100
Displays only if CO
2
se nsor is conne c t e d. Setp oint for Demand Control
Ventilation of space. Above the setpoint, the OA dampers will modulate
open to bring in additional OA to maintain a space ppm level below the
setpoint.
MIN POS 4.4 V 2to10Vdc Displays ON LY if a CO
2
se nsor is NO T conne c ted.
VE N T MAX With 2 --- speed
fan units VENTMAX L (low
speed fan) and VENTMAX
H (hig h sp e ed fan) se t tings
are required
4.4 V 2to10Vdc
or
100 to 9990 cfm
increment by 10
Displays only if a CO
2
se nsor is co nnecte d . Us ed for Vbz (ve nt ilatio n max
cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA and MA). In
A UTO mode dampers controlled by CFM.
VENTMAX L 6V
VENTMAX H 4.4 V
V E N T M I N W ith 2 --- sp ee d
fan units VENTMIN L (low
speed fan) and VENTMIN H
(high speed fan) set
2.8 V 2to10Vdc
or
100 to 9990 cfm
increment by 10
Displays only if a CO
2
sensor is connected. Used for Va (ventilation min
cfm) setpoint. Displays 2 to 10 V if <3 sensors (RA, OA and MA). Va is
only set if DCV is used . This is the vent ilatio n for les s than maximum
occupancy of the space. In A UTO mode dampers controlled by CFM.
VENTMIN L 3.7 V
VENTMIN H 2.8 V
ERV OAT SP 32_F 0to50_F;
increment by 1
Only when AUX1 O = ERV
E X H 1 S E T Wit h 2 --- s pe ed
fan units Exh1 L (low sp e ed
fan) and Exh1 H (high
speed fan) settings are
requi re d
50% 0 to 100%;
increment by 1
SetpointforOAdamperpositionwhenexhaustfan1ispoweredbythe
economizer.
Exh1 L 65%
Exh1 H 50%
E X H 2 S E T Wit h 2 --- s pe ed
fan units Exh2 L (low sp e ed
fan) and Exh2 H (high
speed fan) settings are
requi re d
75% 0 to 100%;
increment by 1
SetpointforOAdamperpositionwhenexhaustfan2ispoweredbythe
economizer. Only used when A UX is set to EHX2.
Exh2 L 80%
Exh2 H 75%
SYSTEM
SETUP
INSTALL 01/01/10 Display orde r = MM/DD/Y Y
Setting order = DD, MM, then YY.
UNITS DEG _F _For_C Sets economizer controller in degrees Fahrenheit or Celsi us.
EQUIPMENT CONV Conventional or HP CON V = conve nt ional; HP O/B = Enable Heat Pump mode. Use AUX2 I
for Heat Pump input from therm ostat or cont rolle r.
AUX2 I W SD/W or HP(O)/HP(B) In CONV mode: SD + Enables configurati on of shutdown (default); W =
Informs controller that system is in heating mode. In HP O/B mode:
HP(O) = energize heat pump on Cool (default); HP(B) = energize heat
pump on Heat.
FAN TYPE 2speed 1 speed/2 speed Sets the economizer controller for operation of 1 speed or 2 speed
supply fan.
FAN CFM 5000cfm 100 to 15000 cfm;
increment by 100
This is the capacity of the RTU. The value is found in the Project
Submittal documents for the specific RTU.
AUX OUT NONE NONE
ERV
EXH2
SYS
S NO N E = not configured (output is not used)
S ERV = Energy Recov e ry Ve nt ilato r
d
S EXH2 = second damper posi ti on relay closure for second exhaust fan
S SYS = use output as an alarm si gnal
OCC INPUT INPUT or ALWAYS Whe n usi ng a setback thermostat wit h occ up a nc y out (24 Vac ) , the 24
V ac is inp ut “IN P UT” to the OCC terminal. If no occ upancy outp ut from
the thermo s tat then change program to “ALWAYS” OR ad a jumpe r from
terminal R to OCC terminal.
LLECON--01SI