Fig. 4 – Installation With Brackets
INSTALLING THE DUCTWORK AND THE
REGISTERS
FULLY DUCTED SYSTEM (T-1)
A200562
Fig. 5 – Fully Ducted System
STALE AIR EXHAUST DUCTWORK:
Install registers in areas where contaminants and humidity are
produced: kitchen, bathrooms, laundry room, etc.
Install registers on an interior wall, 6 to 12 inches away from the
ceiling OR in the ceiling.
Install the kitchen register at least 4 feet away from the range.
Bathroom fans and range hoods can be used to better exhaust stale air.
Homes with more than one level require at least one exhaust register
at the highest level.
FRESH AIR DISTRIBUTION DUCTWORK:
Install registers in bedrooms, dining room, living room and basement.
Install registers in the ceiling OR high on the walls with the airflow
directed towards the ceiling.
If a register must be installed in the floor, direct airflow up the wall.
NOTE: For this type of configuration, the T-1 option must be selected
on the LCD screen when auto-balancing the unit.
EXHAUST DUCTED SYSTEM (T-2)
When performing duct connection to the furnace/AHU, installation must
be done in accordance with all applicable codes and standards. Please
refer to your local building code.
A200563
Fig. 6 – Exhaust Ducted System
STALE AIR EXHAUST DUCTWORK:
Same as for Fully Ducted System.
FRESH AIR DISTRIBUTION:
Connect the fresh air distribution duct of the unit to the furnace/AHU
return duct at least 10 feet away from the furnace/AHU (A+B).
NOTE: This 10-ft. distance applies only in areas where the outside
temperature falls below the freezing point 0°C (32°F).
NOTE: The furnace/AHU blower operation can be synchronized with
the unit (CONNECTION TO THE FURNACE/AHU on p9). It is
recommended, but not essential that the furnace/AHU blower runs when
the unit is in operation.
NOTE: For this type of configuration, the T-2 option must be selected
on the LCD screen when auto-balancing the unit.
ALTERNATE INSTALLATION (T-3):
A200564
Fig. 7 – Exhaust Ducted System – Alternate
INSTALLATION WITH 2 BRACKETS INSTALLATION WITH 4 BRACKETS
WARNING
!
CARBON MONOXIDE HAZARD
Failure to follow this warning could result in serious personal injury or
death.
Never install stale air exhaust register in a room where there is a
combustion device, such as a gas furnace, a gas water heater or a
fireplace. A negative pressure could be created in the area of the fuel
burning unit and draw carbon monoxide into the room. CO can cause
personal injury or death.