EasyManua.ls Logo

Carrier FB4CNP - Page 10

Carrier FB4CNP
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
AIRFLOW PERFORMANCE TABLES (cont)
Table 4 – FB4C Airflow Performance (CFM)
MODEL & SIZE
BLOWER
SPEED
0.10 0.20 0.30 0.40 0.50 0.60
FB4C 018
Tap 5 767 739 702 669 620 565
Tap 4 614 569 534 486 436 398
Tap 3 701 660 616 581 537 499
Tap 2 614 569 534 486 436 398
Tap 1 410 350 304 261 228 203
FB4C 024 / 025
Tap 5 969 936 892 835 763 676
Tap 4 826 795 766 743 706 660
Tap 3 826 795 766 743 706 660
Tap 2 701 660 616 581 537 499
Tap 1 617 592 552 507 472 420
FB4C 030
Tap 5 1108 1090 1065 1034 1009 974
Tap 4 1026 1000 969 938 899 865
Tap 3 1026 1000 969 938 899 865
Tap 2 909 873 842 799 762 724
Tap 1 825 795 757 722 674 634
FB4C 036
Tap 5 1301 1276 1245 1218 1176 1121
Tap 4 1227 1191 1169 1143 1105 1074
Tap 3 1227 1191 1169 1143 1105 1074
Tap 2 1087 1062 1030 1001 966 930
Tap 1 1026 1000 969 938 899 865
FB4C 042
Tap 5 1560 1544 1507 1464 1424 1358
Tap 4 1419 1397 1358 1320 1279 1239
Tap 3 1419 1397 1358 1320 1279 1239
Tap 2 1249 1220 1184 1142 1093 1052
Tap 1 1242 1205 1158 1110 1069 1026
FB4C 048
Tap 5 1743 1712 1679 1642 1610 1574
Tap 4 1669 1634 1599 1564 1531 1499
Tap 3 1669 1634 1599 1564 1531 1499
Tap 2 1452 1413 1377 1339 1308 1271
Tap 1 1300 1256 1221 1182 1142 1101
FB4C 060
Tap 5 1897 1867 1836 1808 1774 1736
Tap 4 1817 1785 1757 1724 1693 1655
Tap 3 1817 1785 1757 1724 1693 1655
Tap 2 1657 1621 1589 1557 1518 1474
Tap 1 1443 1412 1377 1332 1286 1243
FB4C 061
Tap 5 2030 1995 1961 1927 1888 1842
Tap 4 1811 1775 1740 1703 1664 1613
Tap 3 1811 1775 1740 1703 1664 1613
Tap 2 1665 1632 1593 1556 1507 1453
Tap 1 1462 1418 1371 1327 1278 1228
- Shading - Airflow outside 450 cfm/ton.
NOTES:
1. Airflow based upon dry coil at 230v with factoryapproved filter and electric heater (2 element heater sizes 018 through 036, 3 element
heater sizes 042 through 061).
2. For FB4C models, airflow at 208 volts is approximately the same as 230 volts because the multitap ECM motor is a constant torque
motor. The torque doesn’t drop off at the speeds the motor operates.
3. To avoid potential for condensate blowing out of drain pan prior to making drain trap:
Return static pressure must be less than 0.40 in. wc.
Horizontal applications of 042 061 sizes must have supply static greater than 0.20 in. wc.
4. Airflow above 400 cfm/ton on 048061 size could result in condensate blowing off coil or splashing out of drain pan.

Related product manuals