N95ESN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
51
Increase blower speed to reduce temperature rise.
Decrease blower speed to increase temperature rise.
Change the blower heat taps as required to maintain proper temperature
rise for Heating and Cooling as described above. To change blower
motor speed selections for heating mode, remove blower motor lead
from control HEAT terminal. See Fig. 37. Select desired blower motor
speed lead from one of the other motor leads and relocate it/them to
HEAT (heating blower tap) terminal(s). Reconnect original lead on
SPARE terminal.
Adjust Blower Off Delay (Heat Mode)
If desired, the main blower off time delay period may be lengthened or
shortened when operating in the heating mode to provide greater
comfort. For position and location of jumpers on control center, see
Fig. 37 and Fig. 72.
Table 19 – Blower Off Delay Jumper Positions
The blower off delay has four adjustable settings from 90 sec to 180 sec.
See Table 19. The blower off delay jumpers are located on the furnace
control See Fig. 37 and Fig. 72. To change the blower off delay setting,
move the jumper from one set of pins on the control to the pins used for
the desired blower off delay. Factory blower off delay setting is 120 sec.
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect 115vac electrical power before changing speed tap.
(Read following caution before changing taps).
CAUTION
!
UNIT DAMAGE HAZARD
To avoid operating outside the rise range and avoid component damage:
Refer to the Air Delivery Tables to determine which airflows and
settings are allowed for proper heating airflow. DO NOT use the
highlighted settings for Heating airflow. The highlighted settings are to
be used for Cooling and Continuous Fan ONLY.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death,
and/or property damage.
Reinstall manifold pressure tap plug in gas valve to prevent gas leak.
CAUTION
!
FURNACE OVERHEATING HAZARD
Failure to follow this caution may result in reduced furnace life.
Recheck temperature rise. It must be within limits specified on the
rating plate. Recommended operation is at the mid-point of rise range
or slightly above.
PINS 1 AND 2 2 AND 3 3 AND 4 4 AND 5
Time (in sec.) 90 120 150 180
Table 20 – Air Delivery - CFM (With Filter)
UNIT SIZE
WIRE LEAD
COLOR
SPEED
TAPS
2, 3
(Function)
EXTERNAL STATIC PRESSURE (IN.W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0261410
Black Cooling. Do not use for heating 1045 1010 975 935 895 855 810 760 715 670
Yellow Alt Cooling or alt Heating 820 770 730 680 630 585 530 480 435 385
Orange Alt Cooling or alt Heating 655 600 550 495 435 385 335 265 - -
Blue
7
Heating or alt Cooling 605 545 490 435 375 335 255 - - -
Red
7
Alt Cooling. Do not use for heating 480 415 360 305 235 - - - - -
0401410
Gray Cooling. Do not use for heating 1050 1025 1000 975 950 920 895 870 845 820
Yellow Alt Cooling. Do not use for heating 920 890 860 830 805 775 745 715 690 660
Orange Alt Cooling or alt Heating 735 700 665 630 595 555 525 490 450 415
Blue Heating or alt Cooling 695 660 625 590 555 515 480 445 405 370
Red
7
Alt Cooling. Do not use for heating 540 495 455 410 365 320 280 235 - -
0401712
Gray Cooling. Do not use for heating 1180 1140 1100 1055 1010 960 915 860 805 735
Yellow Alt Cooling. Do not use for heating 880 845 810 780 745 710 675 640 600 570
Blue Heating or alt Cooling 650 610 560 515 470 435 395 360 325 265
Orange
7
Alt Cooling. Do not use for heating 525 460 405 350 320 275 210 - - -
Red
7
Alt Cooling. Do not use for heating 515 420 350 310 270 205 - - - -
0601412
Gray Cooling. Do not use for heating 1225 1200 1175 1145 1120 1095 1065 1040 1015 990
Yellow Alt Cooling. Do not use for heating 1105 1080 1050 1020 990 965 935 905 880 850
Blue Heating or alt Cooling 940 910 875 845 810 775 745 710 680 645
Orange Alt Cooling or alt Heating 725 690 650 610 570 530 490 445 405 365
Red
7
Alt Cooling. Do not use for heating 545 495 445 395 345 295 245 - - -
0601714
Gray Cooling. Do not use for heating 1475 1445 1405 1370 1330 1290 1255 1215 1175 1140
Yellow Alt Cooling or alt Heating 1230 1190 1155 1120 1085 1050 1005 970 925 885
Orange Alt Cooling or alt Heating 1070 1030 990 950 920 875 840 800 755 715
Blue Heating or alt Cooling 1020 975 940 900 860 820 775 740 690 650
Red Alt Cooling. Do not use for heating 700 590 535 485 460 390 340 300 275 210
0801716
Gray
5, 6
Cooling. Do not use for heating 1820 1790 1755 1710 1665 1620 1570 1525 1480 1435
Yellow Alt Cooling or alt Heating 1455 1420 1380 1345 1310 1275 1240 1205 1170 1135
Blue Heating or alt Cooling 1335 1295 1260 1220 1185 1150 1110 1075 1040 1005
Orange Alt Cooling or alt Heating 1110 1065 1020 980 935 895 850 810 770 725
Red
7
Alt Cooling. Do not use for heating 425 335 240 - - - - - - -