MAIISMH 12H 8 //MAINMENU/MAINTAIN/
     








17 VOLT_H3 Volts Line Voltage Phase 3
18 ld_amp1 AMPS Load Current Phase 1
19 ld_amp2 AMPS Load Current Phase 2
20 ld_amp3 AMPS Load Current Phase 3
21 bus_volt Volts DC Bus Voltage
   
MAIN_SRD 12H 9 //MAINMENU/MAINTAIN/
     








1 di_tgt % Diuser Target Pos
2 diault - Diuser Fault
3 di_alm - SRD Rotating Stall Alarm
4 srd_a % Calculated SRD Position
5 srd_1 % Calc High Lift SRD Pos
6 srd_2 % Calc Low Lift SRD Pos
7 lift_a ^F Actual Lift
8 lift_1 ^F VDO High Lift Load Line
9 lift_2 ^F VDO Low Lift Load Line
10 strt_tmr min VDO Logic Start Delay
11 stalltmr min SRD Stall Closure Time
   
TEMP_CAL 12H 10 //MAINMENU/MAINTAIN/
     








1 ECW °F Entering Chilled Water
2 ECW_RAW °F ECW Sensor Raw Temp
3 ecw_o -2.0 to 2.0 ^F ECW Temperature Oset -2 2 x
4 LCW °F Leaving Chilled Water
5 LCW_RAW °F LCW Sensor Raw Temp
6 lcw_o -2.0 to 2.0 ^F LCW Temperature Oset -2 2 x
7 ECDW °F Entering Condenser Water
8 ECDW_RAW °F ECDW Sensor Raw Temp
9 ecdw_o -2.0 to 2.0 ^F ECDW Temperature Oset -2 2 x
10 LCDW °F Leaving Condenser Water
11 LCDW_RAW °F LCDW Sensor Raw Temp
12 lcdw_o -2.0 to 2.0 ^F LCDW Temperature Oset -2 2 x
   
MAIOTHER 12H 12 //MAINMENU/
     








1 tran_v Volts 5V Sensor Power Monitor
2 evapp_v Volts Evap Pres Trans Volts
3 condp_v Volts Cond Pres Trans Volts
4 econp_v Volts Econ Pres Trans Volts
5 dip_v Volts Diuser Pres Tran Volts
6 opsmp_v Volts Oil Sump Pres Tran Volts
7 opdis_v Volts Oil Sup Pres Trans Volts
8 evewp_v Volts Evap Enter Water Volts
9 evlwp_v Volts Evap Leave Water Volts
10 cdewp_v Volts Cond Enter Water Volts
11 cdlwp_v Volts Cond Leave Water Volts
12 brgip_v Volts Bearing In Trans Volt
13 brgop_v Volts Bearing Out Trans Volt
14 pumpo_v Volts Pump Output Trans Volt
15 pumpi_v Volts Pump Input Trans Volt
16 last_cpt - Last Cond Pump Run Time
17 pre_chck no/yes - Prestart Check Status
18 gvpos_ok no/yes - GV1 Pos at Startup OK
19 pmppd_ok no/yes - Pump PD at Startup OK
20 hgbp_ok no/yes - ECV Pos at Startup OK
21 dmp_ok no/yes - Damper Pos at Startup OK
22 op_heat no/yes - Oil Pump Req Oil Heater