14
Fig. 8 PremierLink Controller Wiring Combination Temperature and CO
2
Sensor
33ZCT55CO2, 33ZCT56CO2
NOTE: No wire is connected to connector J-5 pin 4. You must relocate a wire from
an unused terminal. Typically one of the red wires from connector J-4 may be used
for this purpose. This pin on J-5 provided 24 VDC power to the combo sensor.