38GLS…G / 38YL-…G Puron
GB - 2
Dimensions and weight
Mod. 38GL 07G - 09G - 12G
Mod. 38YL 07G
Mod. 38GL 18G - 24G
Mod. 38YL 18G
Mod. 38YL 09G -12G
EED EED
EED
B
A
B
C
F
Ø 8,5
C
F
Ø 8,5
C
F
Ø 8,5
A
A
B
EED
A
B
C
F
Ø 8,5
Mod.
38 GL...G 38 YL...G
07 09 12 18 24 07 09 12 18 24
A mm 660 660 660 800 800 660 660 660 800 800
B mm 504 504 504 590 590 504 590 590 590 803
C mm 220 220 220 300 300 220 220 220 300 300
D mm 390 390 390 508 508 390 390 390 508 508
E mm 135 135 135 146 146 135 135 135 146 146
F mm 250 250 250 330 330 250 250 250 330 330
kg 26.5 28 32 45 51 27 32 34 46 52
3
1
2
햲 Outdoor unit
햳 Indoor unit
햴 Height
Connections
Model
07 - 09 12 18 24
Max. height difference 5 m 5 m 10 m 15 m
Max. pipe length 15 m 15 m 30 m 40 m
Minimum nom. thickness
Pipe diameter Minimum nominal
inches - mm thickness (mm)
1/4" - 6.35 0.80
3/8" - 9.52 0.80
1/2" - 12.77 0.80
Table II: Connections
3
1
2
07
9.52 6.35 3/8" 1/4"
09
12
12.77 6.35 1/2" 1/4"
18
24 12.77 6.35 1/2" 1/4"
Pipe diameter
Gas Liquid
(Suction) (Liquid)
mm
All fittings are flare type.
Use only refrigeration
grade pipes, (Cu DHP
type according to
ISO 1337), seamless,
degreased, deoxidized
and suitable for operating
pressures of at least
4200 kPa and with a
burst pressure of
20700 kPa.
Under no circumstances
must sanitary type
copper pipe be used.
Model
Pipe diameter
Gas Liquid
(Suction) (Liquid)
inches
Mod. 38YL 24G