EasyManua.ls Logo

Carrier REFRIGERANT R-410A - Page 34

Carrier REFRIGERANT R-410A
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Copyright 2009 Carrier Corp • 7310 W. Morris St. • Indianapolis, IN 46231 Printed in Mexico Edition Date: 09/09 Catalog No: 40RU-03SI
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: New
34
Legend and Notes for Tables 10A and 10C
LEGEND
NOTES:
1. Maximum allowable fan speed for size 25 units is 1200 rpm .
Maximum allowable fan speed for size 28 and 30 units is 1100
rpm.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See table at right for factory-supplied filter
pressure drop.
3. Refer to fan motor and drive tables for additional data.
FACTORY-SUPPLIED PRESSURE DROP — ENGLISH
Legend and Notes for Tables 10B and 10D
LEGEND
ESP — External Static Pressure
NOTES:
1. Maximum allowable fan speed for size 25 units is 20 r/s.
Maximum allowable fan speed for size 28 and 30 units is 18.3 r/s.
2. Fan performance is based on deductions for wet coil, clean
51-mm filters, and unit casing. See table at right for factory-sup-
plied filter pressure drop.
3. Refer to fan motor and drive tables for additional data.
FACTORY-SUPPLIED PRESSURE DROP — SI
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure
UNIT
AIRFLOW
(Cfm)
PRESSURE DROP
(in. wg)
40RUA*25
40RUS*25
6,000 0.12
8,000 0.19
10,000 0.26
40RUA*28
40RUS*28
7,500 0.15
10,000 0.22
12,500 0.30
40RUA*30
40RUS*30
9,000 0.19
12,000 0.29
15,000 0.40
UNIT
AIRFLOW
(L/s)
PRESSURE DROP
(Pa)
40RUA*25
40RUS*25
2900 32
3800 47
4700 64
40RUA*28
40RUS*28
3500 36
4700 55
5900 76
40RUA*30
40RUS*30
4250 47
5650 71
7050 98

Related product manuals