2 - MACHINE ILLUSTRATIONS
2.1 - Typical chiller detail
Fig. 2 - Water header side
1
2
3
4
5
6
7
8
9
10
11
12
Fig. 3 - Control panel side
2
3
Legend
1 Condenser
2 Cooling water outlet
3 Chilled water flow switch
4 Chilled water outlet
5 Evaporator
6 Chilled water inlet
7 Cooling water inlet
8 Purge pump
9 Steam inlet
10 Generator pressure switch
11 Generator
12 Absorber
1
Legend
1 Drain outlet
2 Hot water outlet
3 Control panel
1 - PRECAUTIONS - CONT.
1.2 - High-temperature - high-voltage caution
Do not touch the chiller during operation since its surface
becomes hot.
Do not touch the absorbent pump, the refrigerant pump,
and the purge pump during operation, since their surface
becomes hot.
Do not touch the junction box during operation, since it
contains high-voltage wiring.
Do not touch the terminal box during operation, since it
contains high-voltage wiring.
1.3 - Environmental requirements
1.3.1 - Installation considerations
The 16TJ absorption chiller is designed for indoor installation
in a machine room. The protection rating of the chiller is IP40.
Room temperature should be maintained between 5°C and
40°C to protect against solution crystallization during chiller
shutdown. The humidity in the machine room must be kept
below 90%.
1.3.2 - Field wiring
The machines should be connected to a power source that
complies with overvoltage category III (IEC 60664). All other
wiring should comply with overvoltage category II.
1.3.3 - Altitude
Please install the absorption chiller at a maximum height of
1000 m above sea level. If the location is higher than 1000 m
above sea level, please contact your local Carrier office.
1.4 - Water treatment
Refer to chapter 4 "Maintenance”.