EasyManua.ls Logo

Carrier TOUCHPILOT 30KAV - Configuration Menu: User and Pump Details; User Configuration Details; Pump Configuration Details

Carrier TOUCHPILOT 30KAV
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
General Conguration Menu – GEN_CONF(continued)
No. Name Status Default Unit Displayed text* Description
19 ln_start 00:00 00:00 - Low Noise Start Hour Low noise option / Fan speed limitation
(beginning of Low Noise mode)
20 ln_end 00:00 00:00 - Low Noise End Hour Low noise option / Fan speed limitation
(end of Low Noise mode)
21 ln_limit 60 to 100 75 % Low Noise Fan freq limit Fan speed during the time when the Low Noise
option is enabled
*Depends on the selected language (English by default).
Pump Conguration Menu – PUMPCONF
No. Name Status Default Unit Displayed text* Description
1 cpumpseq 0 to 4 0 - Cooler Pumps Sequence Evaporator pumps' sequence
2 0 = No Pump 0 = No Pump
3 1 = One Pump Only 1 = One Pump Only
4 2 = Two Pumps Auto 2 = Two Pumps Auto (units with two pumps)
5 3 = Pump#1 Manual 3 = Pump#1 Manual
6 4 = Pump#2 Manual 4 = Pump#2 Manual
7 pump_del 24 to 3000 48 hour Pump Auto Rotation Delay Pump auto rotation delay (units with two
pumps and 'auto control' enabled)
8 pump_per no/yes no - Pump Sticking Protection Pump anti-sticking protection
9 pump_sby no/yes no - Stop Pump During Standby Pump stopped during standby
10 pump_loc no/yes yes - Flow Checked If Pump O Water ow is checked when the pump is o
11 stopheat no/yes no - Cooler Pump O In Heat Not applicable to this unit
12 stopcool no/yes no - Cond Pump O In Cool Not applicable to this unit
13 varipump 1 to 4 1 - VSPump regulation cong Variable speed pump regulation conguration:
1 = Control variable speed pump on delta
temperature
2 = Control variable speed pump on delta
pressure (applicable to internal pumps only)
3 = Control variable speed pump on constant
output pressure
4 = Variable speed pump xed speed control
*Depends on the selected language (English by default).
User Conguration Menu – USERCONF
No. Name Status Default Unit Displayed text* Description
1 use_pass 1 to 9999 11 - User Password User password (provides access to basic
conguration parameters)
2 lng_list 0 to 1 1 - Language List Language list selection
3 0 = eng/spa/fre/ger/dut Languages available on the user interface
when "Language list" is set to "0"
4 chi/ita/por/rus/und
5 1 = eng/spa/fre/ger/dut Languages available on the user interface
when "Language list" is set to "1"
6 tur/ita/por/rus/und
*Depends on the selected language (English by default).

Related product manuals