VVT Zone Controller 57
(Occupied or Unoccupied, depending on mode) The current programmed
R:
setpoint adjusted by any offset that may be in effect.
0 to 120°F
ā The cooling capacity learned by Learning Adaptive Optimal Start
that is required to bring the space temperature down to the occupied cooling setpoint prior to
the occupied time.
ā The heating capacity learned by Learning Adaptive Optimal Start
that is required to bring the space temperature up to the occupied heating setpoint prior to the
occupied time.
D: ā Minimum separation that must be maintained between the heating
and cooling setpoints.
R:
4°F
2 to 10°F
ā The earliest time, prior to occupancy, at which the Optimal Start function may
begin to adjust the effective setpoints to achieve the occupied setpoints by the time scheduled
occupancy begins. Enter 0 to disable Optimal Start.
Optimal Start is automatically disabled when
>
>
>
>
is set to either
or
D:
.
R:
1 hr
0 to 4 hr
ā The method used to change from unoccupied to occupied setpoint.
Options:
ā Unit will not change to occupied setpoint until the scheduled time or the unit goes into
an occupied mode. Setpoints do not ramp, but change immediately from unoccupied to
occupied values.
ā Unit changes to occupied setpoints at a variable time prior to the
occupied time, which is calculated by the current error between space temperature and the
appropriate heating or cooling setpoint. At that time, the setpoints do not ramp, but change
immediately from unoccupied to occupied values.
ā Unit gradually changes to occupied setpoints by adjusting the
unoccupied setpoints over a specified period of time to achieve the occupied setpoint by the
time scheduled occupancy begins.
When selecting
or
D:
, you MUST set all Learning Adaptive Optimal
Start transition factors to 0.
R:
Temperature
Compensated
None
Temperature
Compensated
Learning Adaptive
Heat Start K factor (min/deg)
ā If
is
D: , this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is below the occupied heating setpoint (including any setpoint offset).
R:
15.00
0 to 99
Cool Start K factor (min/deg)
ā If
is
D: , this is the time in
minutes per degree that the equipment starts before the occupied period when the space
temperature is above the occupied cooling setpoint (including any setpoint offset).
R:
15.00
0 to 99
D: ā The value by which the occupied setpoints are expanded when the space
occupancy sensor indicates that the space is unoccupied. If 0, the unoccupied setpoints are
used.
R:
0°F
0 to 15°F
Occupied RH Control Setpoint
ā If
is set to
and
is
set to
, this is the relative humidity setpoint during occupancy. The air source mode must
be
or
and the terminal mode must be
or
D:
before the dehumidification
function can be active.
R:
65%rh
0 to 100%rh
ā If
is set to
and
is set to
D:
, this is the value that the CO2 sensor must exceed to begin the DCV control function.
This value should be set to approximately 75 ppm above the outdoor air CO2 level.
R:
500ppm
0 to 9999 ppm