Appendix A: VVT Zone Controller Points/Properties
64 VVT Zone Controller
Outdoor Air Temperature Source
– The source of the outside air temperature.
R:
N/A
Local
Network
Linkage
Locked Value
The status of the terminal heat delay. R:
Inactive/Active
If
is
, this is the remaining delay time. R:
0 to 60 minutes
– The system cool demand level being received over the
network.
R:
0 to 3
– The system heat demand level being received over the
network.
R:
0 to 3
Calculated DCV Damper Position –
If the controller is in IAQ Override mode, this is the
calculated minimum damper position that will be maintained to satisfy the mode.
R: 0 to 100%
Calculated Dehumidify Dmpr Position –
If the controller is in Dehumidify mode, this is
the calculated minimum damper position that will be maintained to satisfy the mode.
R: 0 to 100%
– Set this to
to reset an active
and restart the
Filter
Service Alarm Timer
. After the alarm returns to normal, this automatically changes to
.
D:
R:
Off
On/Off
- The physical state of the
input. R: Open/Closed
– Determines the occupancy state of the controller and can be set over
the network by another device or third party BAS.
Options:
•
– Occupancy is determined by a configured schedule.
•
– The controller is always in the occupied mode.
•
– The controller is always in the unoccupied mode.
If
is set to either
or
, the
routine
is automatically disabled.
D:
R:
Inactive
Inactive
Occupied
Unoccupied
– The controller's occupancy status based on the schedule. R: Occupied/Unoccupied
–
indicates if a user pushed the sensor's override button to
override the occupancy state.
R: Off/Active
– The amount of time remaining in an override period. R: 0 to 480 minutes
– The physical state of the controller's
input. R: Inactive
Active Unoccupied/Stdby
The current state of the
network input. D:
R:
Unoccupied
Unoccupied/Occupied