Fig. 26 — Typical Smoke Detector System Wiring
Sensor and Controller Tests
SENSOR ALARM TEST
The sensor alarm test checks a sensor’s ability to signal an alarm
state. This test requires the use of a field-provided SD-MAG test
magnet.
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of the sensor
housing for seven seconds.
2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the test magnet against the sensor
housing for two seconds.
4. Verify that the sensor’s Alarm LED turns off.
CONTROLLER ALARM TEST
The controller alarm test checks the controller’s ability to initiate
and indicate an alarm state.
Controller Alarm Test Procedure
1. Press the controller’s test/reset switch for seven seconds.
2. Verify that the controller’s Alarm LED turns on.
3. Reset the sensor by pressing the test/reset switch for two
seconds.
4. Verify that the controller’s Alarm LED turns off.
DIRTY CONTROLLER TEST
The dirty controller test checks the controller’s ability to initiate a
dirty sensor test and indicate its results.
Dirty Controller Test Procedure
1. Press the controller’s test/reset switch for two seconds.
2. Verify that the controller’s Trouble LED flashes.
DIRTY SENSOR TEST
The dirty sensor test provides an indication of the sensor’s ability
to compensate for gradual environmental changes. A sensor that
can no longer compensate for environmental changes is consid-
ered 100% dirty and requires cleaning or replacing. Use a field
provided SD-MAG test magnet to initiate a sensor dirty test. The
sensor’s Dirty LED indicates the results of the dirty test as shown
in Table 2.
BLK
BLK
BRN
1
4
3
2
DDC
X
C
G
W2
1
2
3
4
5
4
6
5
3
2
1
CLO1/
COMP1
BRN
VIO
1
2
3
PMR
1
2
3
4
5
6
7
8
4
6
8
7
5
3
2
1
CONTL
BOARD
WHT
ORN
BRN
BRN
BLK
RED
9
9
RED
REMOTE
SHUTDOWN
UNIT
SHUTDOWN
SMOKE
SHUTDOWN
24V OUT
C
SMOKE
ALARM
JMP4
JMP3
JMP1
OCCUPANCY
JMP2
R
C
BLU
GRA
10
10
RED
11
11
RED
12
12
DDC
PNK
T'STAT
4
3
2
1
BRN
GRN
PNK
WHT
C
COFS (FIOP)
BLU
BLU
BLU
RED
BRN
BRN
RED
BRN
COFS
BRN
LCTB-C
RED
LOGIC
BRN
COFS(FIOP)
C
48HC500010
TRAN
24V
BRN
GRA
C
BRN
BRN
CLO1 TERM BD
3
RED
FROM POWER SCHEMATIC
24V
GRN/YEL
BRN
TRAN
BRN
CONTROL BD
24V
5
CB
3.2 AMPS
ORN BLU
RED
BRN
WHT
YEL
PNK
RED
GRA
BRN
FOR FIELD USE
RED
PNK
BRN
COM
24V
CONT
PMR
FIOP/ACCY
RED
BRN
CCHTS
460/575V ONLY
CCHR
TDR BD
3
BRN
FPT
BLK
SMOKE CONTROL
MODULE
FIOP/ACCESSORY
16
10
9
ORN
BRN
POWER
24 VAC
6
17
14
3
5
4
NC
NO
BLU
TROUBLE
NC
ALARM
NO
RJ-45
RETURN
SMOKE
SENSOR
RJ-45
SUPPLY
SMOKE
SENSOR
FIOP/
ACCESSORY
RED
GRA
YEL
GRN
PNK
1
2
4
3
6
7
8
9
PL19-
WHT
5
GRA
GRA
ORN
BRN
BLU
RED
GRA
YEL
GRA
PNK
WHT
RED
BRN
BLK
A
E
F
C
B
D
IMPORTANT: Failure to follow this caution may result in
personnel and authority concern.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary equipment
from the controller before performing the test. If the duct
detector is connected to a fire alarm system, notify the
proper authorities before performing the test.
IMPORTANT: Failure to follow this caution may result in
personnel and authority concern.
This test places the duct detector into the alarm state. Dis-
connect all auxiliary equipment from the controller before
performing the test. If the duct detector is connected to a
fire alarm system, notify the proper authorities before per-
forming the test.
IMPORTANT: Failure to follow this caution may result in
personnel and authority concern.
Pressing the controller’s test/reset switch for longer than
seven seconds will put the duct detector into the alarm state
and activate all automatic alarm responses.
IMPORTANT: Failure to follow this caution may result in
personnel and authority concern.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector into the
alarm state and activate all automatic alarm responses.