To convert BHP to watts, use 84% motor efficiency. To convert BHP to watts, use 84% motor efficiency.
Table D — 48LC**05 Direct Drive (Horizontal)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
1000 0.12 0.14
1200 0.00 0.21
1400
1500
1600
1700
1800
1900
2000
2
1000 0.89 0.43
1200 0.60 0.40
1400 0.30 0.36
1500 0.16 0.34
1600 0.02 0.32
1700
1800
1900
2000
3
1000 1.14 0.52
1200 0.96 0.59
1400 0.70 0.65
1500 0.54 0.64
1600 0.37 0.61
1700 0.18 0.61
1800
1900
2000
4
1000 1.15 0.52
1200 1.01 0.59
1400 0.86 0.65
1500 0.79 0.69
1600 0.72 0.72
1700 0.64 0.75
1800 0.56 0.79
1900 0.47 0.82
2000 0.37 0.84
5
1000 1.15 0.53
1200 1.02 0.60
1400 0.88 0.67
1500 0.81 0.70
1600 0.74 0.74
1700 0.67 0.78
1800 0.59 0.82
1900 0.51 0.86
2000 0.42 0.92
Table E — 48LC**05 Direct Drive (Vertical)
SPEED
(TORQUE) TAP
CFM ESP BHP
1
1000 0.08 0.11
1200
1400
1500
1600
1700
1800
1900
2000
2
1000 0.79 0.37
1200 0.49 0.34
1400 0.20 0.31
1500 0.05 0.29
1600
1700
1800
1900
2000
3
1000 1.11 0.50
1200 0.90 0.57
1400 0.59 0.62
1500 0.40 0.59
1600 0.20 0.52
1700
1800
1900
2000
4
1000 1.12 0.50
1200 0.95 0.57
1400 0.79 0.63
1500 0.70 0.67
1600 0.61 0.70
1700 0.52 0.73
1800 0.41 0.75
1900 0.30 0.77
2000
5
1000 1.13 0.51
1200 0.97 0.58
1400 0.81 0.65
1500 0.73 0.68
1600 0.64 0.72
1700 0.55 0.75
1800 0.46 0.79
1900 0.35 0.82
2000 0.25 0.89