APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — SERVICE TEST
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS PAGE NO.
TEST Service Test Mode ON/OFF MAN_CTRL
STOP Local Machine Disable YES/NO UNITSTOP config 29,30,33,75
S.STP Soft Stop Request YES/NO SOFTSTOP forcible 29,30
FAN.F Supply Fan Request YES/NO SFANFORC forcible 29,30
INDP TEST INDEPENDENT OUTPUTS
HUM.R Humidifier Relay ON/OFF HUMR_TST 29,30
UVC.R UV-C Lamp Relay ON/OFF UVCR_TST 30
ALRM Remote Alarm / Aux Relay ON/OFF ALRM_TST 30
FANS TEST FANS
F.M OD Fan Test Mode Automatic? YES/NO FANAUTO 29,30
E.POS Econ 1 Out Act.Cmd.Pos. 0 to 100 % ECONFANS 29,30
SF.BY Supply Fan Bypass Relay ON/OFF SFBY_TST 30
S.VFD Supply Fan Commanded % 0 to 100 % SFVFDTST 30
PE.BY Power Exhaust Bypass Rly ON/OFF PEBY_TST 30
E.VFD Exhaust Fan Commanded % 0 to 100 % EFVFDTST 30
A.VFD MtrMaster A Commanded % 0 to 100 % OAVFDTST 30
B.VFD MtrMaster B Commanded % 0 to 100 % OBVFDTST 30
CDF.1 Condenser Fan Output 1 ON/OFF CDF1_TST 30
CDF.2 Condenser Fan Output 2 ON/OFF CDF2_TST 30
CDF.3 Condenser Fan Output 3 ON/OFF CDF3_TST 30
CDF.4 Condenser Fan Output 4 ON/OFF CDF4_TST 30
CDF.5 Condenser Fan Output 5 ON/OFF CDF5_TST 30
AC.T.C CALIBRATE TEST-ACTUATORS
EC1.C
Econ 1 Out Act.Cmd.Pos. 0 to 100 % ECON1TST 30
E1.CL Economizer Calibrate Cmd YES/NO ECONOCAL 30
E1C.A Econ 1 Out Act Ctl Angle 0 to 100 ECONCANG 30
EC2.C Econ 2 Ret Act.Cmd.Pos. 0 to 100 % ECON2TST 30
E2.CL Economzr 2 Calibrate Cmd YES/NO ECON2CAL 30
E2C.A Econ 2 Ret Act Ctl Angle 0 to 100 ECN2CANG 30
EC3.C Econ 3 Out Act.Cmd.Pos. 0 to 100 % ECON3TST 30
E3.CL Economzr 3 Calibrate Cmd YES/NO ECON3CAL 30
E3C.A Humidifier Act.Ctrl.Ang. 0 to 100 HUMDCANG 30
HTC.C Ht.Coil Command Position 0 to 100 % HTCLACTS 30
HT.CL Heating Coil Act.Cal.Cmd YES/NO HCOILCAL 30
HTC.A Heat Coil Act.Ctl.Angle 0 to 100 HTCLCANG 30
HMD.C Humidifier Command Pos. 0 to 100 % HUMD_TST 30
HM.CL Humidifier Act. Cal. Cmd YES/NO HUMIDCAL 30
HMD.A Humidifier Act.Ctrl.Ang. 0 to 100 HUMDCANG 30
SRCH SEARCH FOR SERIAL NUMBER
ACTV
Belimo Serial Num Search
YES/NO
BELSERCH
30
ECN.1
Economizer 1 Search
YES/NO
EC1SERCH
forcible 30
ECN.2
Economizer 2 Search
YES/NO
EC2SERCH
forcible 30
ECN.3
Economizer 3 Search
YES/NO
EC3SERCH
forcible 30
HUMD
Humidifier Valve Search
YES/NO
HUMSERCH
forcible 30
HT.CL
Heat Coil Valve Search
YES/NO
HTCSERCH
forcible 30
HMZR TEST HUMIDIMIZER
RHV
HumidiMizer 3-way Valve Off/On RHVH_TST
30,32
C.EXV
Condenser EXV Position 0 to 100 % CEXVHTST
30,32
B.EXV
Bypass EXV Position 0 to 100 % BEXVHTST
30,32
C.CAL
Condenser EXV Calibrate Off/On CEXV_CAL
30,32
B.CAL
Bypass EXV Calibrate Off/On BEXV_CAL
30,32
EXVS TEST CIRCUIT EXVS
A1.EX
Circuit A EXV 1 Position 0 to 100 % A_X1_TST
30
A2.EX
Circuit A EXV 2 Position 0 to 100 % A_X2_TST
30
B1.EX
Circuit B EXV 1 Position 0 to 100 % B_X1_TST
30
B2.EX
Circuit B EXV 2 Position 0 to 100 % B_X2_TST
30
A1.CL
Cir A EXV 1 Calibrate Off/On A_X1_CAL
30
A2.CL
Cir A EXV 2 Calibrate Off/On A_X2_CAL
30
B1.CL
Cir B EXV 1 Calibrate Off/On B_X1_CAL
30
B2.CL
Cir B EXV 2 Calibrate Off/On B_X2_CAL
30
COOL TEST COOLING
E.POS Econ 1 Out Act.Cmd.Pos. 0 to 100 % ECONCOOL 30,32
SP.SP Static Pressure Setpoint 0 to 5 "H2O SPSPCTST 30,32
CL.ST Requested Cool Stage 0 to 8 CLST_TST 30,32
MLV Minimum Load Valve Relay Off/On MLV_TST 30
A1 Compressor A1 Relay Off/On CMPA1TST 30
A1.CP Compressor A1 Capacity 20 to 100 % A1CAPTST 30
A1.B1 Two Circuit Start A1,B1 Off/On CMPABTST 30
A2 Compressor A2 Relay Off/On CMPA2TST 30
A3 Compressor A3 Relay Off/On CMPA3TST 30
A4 Compressor A4 Relay Off/On CMPA4TST 30
B1 Compressor B1 Relay Off/On CMPB1TST 30
B2 Compressor B2 Relay Off/On CMPB2TST 30
B3 Compressor B3 Relay Off/On CMPB3TST 30
B4 Compressor B4 Relay Off/On CMPB4TST 30
RHV
HumidiMizer 3-way Valve
Off/On
RHVC_TST
30,33,159
C.EXV
Condenser EXV Position 0 to 100 % CEXVCTST
30,33
B.EXV
Bypass EXV Position 0 to 100 % BEXVCTST
30,33