179
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
GEN.I GENERAL INPUTS
PWR.F Power Fault Input Normal/Alarm PWRFAULT forcible
MFL.S Main Filter Status Input Clean/Dirty FLTS forcible
PFL.S Post Filter Status Input Clean/Dirty PFLTS forcible
G.FAN Fan request from IGC Off/On IGCFAN
REMT Remote Input State Off/On RMTIN forcible
ENTH Enth. Switch Read High? No/Yes ENTH forcible
S.FN.S Supply Fan Status Switch Off/On SFS forcible
FRZ.S Freeze Status Switch Normal/Alarm FRZ forcible
PP.SW Plenum Press.Safety Sw. Low/High PPS forcible
AP.SS Air Press.Safety Switch Low/High APS forcible
DL.S1 Demand Limit Switch 1 Off/On DMD_SW1 forcible
DL.S2 Demand Limit Switch 2 Off/On DMD_SW2 forcible
DH.IN Dehumidify Switch Input Off/On DHDISCIN forcible
SF.BY Supply Fan Bypass Input Off/On SFBYIN forcible
PE.BY Power Exh. Bypass Input Off/On PEBYIN forcible
UVC.S UV-C Lamp Status Switch Off/On UVCSTS forcible
FD.BK COMPRESSOR FEEDBACK
HPS.A Circ A High Press. Switch Low/High CIRCAHPS
HPS.B Circ B High Press. Switch Low/High CIRCBHPS
CS.A1 Compressor A1 Feedback Off/On CSB_A1
CS.A2 Compressor A2 Feedback Off/On CSB_A2
CS.A3 Compressor A3 Feedback Off/On CSB_A3
CS.A4 Compressor A4 Feedback Off/On CSB_A4
CS.B1 Compressor B1 Feedback Off/On CSB_B1
CS.B2 Compressor B2 Feedback Off/On CSB_B2
CS.B3 Compressor B3 Feedback Off/On CSB_B3
CS.B4 Compressor B4 Feedback Off/On CSB_B4
STAT THERMOSTAT INPUTS
G Thermostat G Input Off/On G forcible
W1 Thermostat W1 Input Off/On W1 forcible
W2 Thermostat W2 Input Off/On W2 forcible
Y1 Thermostat Y1 Input Off/On Y1 forcible
Y2 Thermostat Y2 Input Off/On Y2 forcible
FIRE FIRE-SMOKE INPUTS
FSD Fire Shutdown Input Normal/Alarm FSD forcible
PRES Pressurization Input Normal/Alarm PRES forcible
EVAC Evacuation Input Normal/Alarm EVAC forcible
PURG Smoke Purge Input Normal/Alarm PURG forcible
REL.H RELATIVE HUMIDITY
OA.RH Outside Air Rel. Humidity 0 to 100 % OARH forcible
OA.EN Outdoor Air Enthalpy -20 to 10000 OAE
OA.DP OutsideAir Dewpoint Temp -40 to 240 dF OADEWTMP
RA.RH Return Air Rel. Humidity 0 to 100 % RARH forcible
RA.EN Return Air Enthalpy -20 to 10000 RAE
SP.RH Space Relative Humidity 0 to 100 % SPRH forcible
MA.RH Mixed Air Rel.Humidity 0 to 100 % MARH forcible
SP.EN Space Enthalpy -20 to 10000 SPE
AIR.Q AIR QUALITY SENSORS
IAQ.I IAQ - Discrete Input Low/High IAQIN forcible
IAQ IAQ - PPM Return CO2 0 to 5000 IAQ forcible
OAQ OAQ - PPM Return CO2 0 to 5000 OAQ forcible
DAQ Diff.Air Quality in PPM 0 to 5000 DAQ
IQ.P.O IAQ Min.Pos. Override 0 to 100 % IAQMINOV forcible
CFM CFM SENSORS
O.CFM Outside Air CFM 0 to 65000 CFM OACFM
R.CFM Return Air CFM 0 to 65000 CFM RACFM
S.CFM Supply Air CFM 0 to 65000 CFM SACFM
D.CFM Fan Track Control D.CFM -20000 to 20000 CFM DELTACFM
E.CFM Exhaust Air CFM 0 to 65000 CFM EACFM
RSET RESET INPUTS
SA.S.R Supply Air Setpnt. Reset 0 to 20 ^F SASPRSET forcible
SP.RS Static Pressure Reset 0 to 15 SPRESET forcible
4-20 4-20 MILLIAMP INPUTS
IAQ.M IAQ Milliamps 0 to 20 ma IAQ_MA
OAQ.M OAQ Milliamps 0 to 15 ma OAQ_MA
SP.R.M SP Reset milliamps 0 to 20 ma SPRST_MA
DML.M 4-20 ma Demand Signal 0 to 20 ma DMDLMTMA forcible
EDR.M EDT Reset Milliamps 0 to 20 ma EDTRESMA
ORH.M OARH Milliamps 0 to 20 ma OARH_MA
SRH.M SPRH Milliamps 0 to 20 ma SPRH_MA
RRH.M RARH Milliamps 0 to 20 ma RARH_MA
MRH.M MARH milliamps 0 to 20 ma MARH_MA
SAC.M SACFM Milliamps 0 to 20 ma SACFM_MA
SA.M.T Supply Air CFM Trim (ma) -2 to 2 SAMATRIM config
RAC.M RACFM Milliamps 0 to 22 ma RACFM_MA
RA.M.T Return Air CFM Trim (ma) -2 to 2 RAMATRIM config
EAC.M EACFM milliamps 0 to 22 ma EACFM_MA
EA.M.T Exh. Air CFM Trim (ma) -2 to 2 EAMATRIM config
OAC.M OACFM Milliamps 0 to 22 ma OACFM_MA
OA.M.T Outside Air CFM Trim(ma) -2 to 2 OAMATRIM config
BP.M BP Milliamps 0 to 22 ma BP_MA
BP.M.T Bldg. Pressure Trim (ma) -2 to 2 BPMATRIM config
SP.M SP Milliamps 0 to 22 ma SP_MA
SP.M.T Static Press. Trim (ma) -2 to 2 SPMATRIM config
MF.DP Main Filter DeltaPressMa 0 to 22 ma MF_DP_MA
PF.DP Post Filter DeltaPressMa 0 to 22 ma PF_DP_MA