184
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
*The display text changes depending on the remote switch configuration (Configuration
UNIT
RM.CF). If RM.CF is set to 0 (No Remote Switch), then the display
text will be “On” or “Off.” If RM.CF is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or “Unoccupied.” If RM.CF is set to 2 (Start/Stop),
then the display text will be “Stop” or “Start.” If RM.CF is set to 3 (Override Switch), then the display text will be “No Override” or “Override.”
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
BP BUILDING PRESS. CONFIGS
BP.CF Building Press. Config 0 to 2 BLDG_CFG 0* 28,80,81
BP.S Building Pressure Sensor Disable/Enable BPSENS Disable* 80,81
BP.R Bldg. Press. (+/-) Range 0.1 to 0.25 "H2O BP_RANGE 0.25 80,81
BP.SP Building Pressure Setp. -0.25 to 0.25 "H2O BPSP 0.05 28,80,81,124
BP.SO BP Setpoint Offset 0 to 0.5 "H2O BPSO 0.05 28,80,81
B.V.A VFD/ACTUATOR CONFIG
B.V.ABP.FS VFD Fire Speed 0 to 100 % BLDGPFSO 100 28,80,81,83
B.V.ABP.MN VFD Minimum Speed 0 to 100 % BLDGPMIN 10 28,80,81
B.V.ABP.MX VFD Maximum Speed 0 to 100 % BLDGPMAX 100 28,81
FAN.T FAN TRACKING CONFIG
FAN.TFT.CF Fan Track Learn Enable No/Yes DCFM_CFG No 28,81
FAN.TFT.TM Fan Track Learn Rate 5 to 60 min DCFMRATE 15 28,81
FAN.TFT.ST Fan Track Initial DCFM -20000 to 20000 CFM DCFMSTRT 2000 28,81
FAN.TFT.MX Fan Track Max Clamp 0 to 20000 CFM DCFM_MAX 4000 28,81
FAN.TFT.AD Fan Track Max Correction 0 to 20000 CFM DCFM_ADJ 1000 28,81
FAN.TFT.OF Fan Track Internl EEPROM -20000 to 20000 CFM DCFM_OFF 0 28,81
FAN.TFT.RM Fan Track Internal RAM -20000 to 20000 CFM DCFM_RAM 0 28,81
FAN.TFT.RS Fan Track Reset Internal No/Yes DCFMRSET No 28,81
FAN.C SUPPLY, RET/EXH FAN CFG
FAN.CSCF.C Supply Air CFM Config 1 to 2 SCFM_CFG 2 81
FAN.CREF.C Ret/Exh Air CFM Config 1 to 2 RECFMCFG 2 81
FAN.CSCF.S Supply Air CFM Sensor Disable/Enable SCFMSENS Disable* 81
FAN.CRCF.S Return Air CFM Sensor Disable/Enable RCFMSENS Disable* 81
FAN.CECF.S Exhaust Air CFM Sensor Disable/Enable ECFMSENS Disable* 81
B.PID BLDG.PRESS.PID CONFIGS
B.PIDBP.TM Bldg.Pres.PID Run Rate 1 to 60 Seconds BPIDRATE 10 81
B.PIDBP.P Bldg.Press. Prop. Gain 0 to 5 BLDGP_PG 0.5 81
B.PIDBP.I Bldg.Press. Integ. Gain 0 to 2 BLDGP_IG 0.5 81
B.PIDBP.D Bldg.Press. Deriv. Gain 0 to 5 BLDGP_DG 0.3 81
D.LV.T COOL/HEAT SETPT. OFFSETS
D.LV.TL.H.ON Dmd Level Lo Heat ON 0 to 2 ^F DMDLHON 1.5 27,51,63
D.LV.TH.H.ON Dmd Level(+) Hi Heat ON 0.5 to 20 ^F DMDHHON 0.5 51,63
D.LV.TL.H.OF Dmd Level(-) Lo Heat OFF 0.5 to 2 ^F DMDLHOFF 1 27,51,63
D.LV.TL.C.ON Dmd Level Lo Cool ON 0 to 2 ^F DMDLCON 1.5 51,63
D.LV.TH.C.ON Dmd Level(+) Hi Cool ON 0.5 to 20 ^F DMDHCON 0.5 51,63
D.LV.TL.C.OF Dmd Level(-) Lo Cool OFF 0.5 to 2 ^F DMDLCOFF 1 51,63
D.LV.TC.T.LV Cool Trend Demand Level 0.1 to 5 ^F CTRENDLV 0.1 51,63
D.LV.TH.T.LV Heat Trend Demand Level 0.1 to 5 ^F HTRENDLV 0.1 51,63
D.LV.TC.T.TM Cool Trend Time 30 to 600 Seconds CTRENDTM 120 51,63
D.LV.TH.T.TM Heat Trend Time 30 to 600 Seconds HTRENDTM 120 51,63
DMD.L DEMAND LIMIT CONFIG.
DMD.LDM.L.S Demand Limit Select 0 to 3 DMD_CTRL 0 40,45,55,56
DMD.LD.L.20 Demand Limit at 20 ma 0 to 100 % DMT20MA 100 40,56
DMD.LSH.NM Loadshed Group Number 0 to 99 SHED_NUM 0 56
DMD.LSH.DL Loadshed Demand Delta 0 to 60 % SHED_DEL 0 56
DMD.LSH.TM Maximum Loadshed Time 0 to 120 Minutes SHED_TIM 6 56
DMD.LD.L.S1 Demand Limit Sw.1 Setpt. 0 to 100 % DLSWSP1 80 40,55,56
DMD.LD.L.S2 Demand Limit Sw.2 Setpt. 0 to 100 % DLSWSP2 50 40,55,56