187
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — TIMECLOCK
MODE — OPERATING MODES
MODE — ALARMS
ITEM EXPANSION RANGE UNITS CNN POINT DEFAULTS PAGE NO.
TIME TIME OF DAY
HH.MM Hour and Minute 0 to 65535 TIME 97,98
DATE MONTH,DATE,DAY AND YEAR
MNTH Month of Year 1 to 12 MOY 97,98
DOM Day of Month 1 to 31 DOM 97,98
DAY Day of Week 1 to 7 DOWDISP 97,98
YEAR Year e.g. 2013 YOCDISP 97,98
SCH.L LOCAL TIME SCHEDULE
PER.1 PERIOD 1 27,29,97,98
PER.1DAYS DAY FLAGS FOR PERIOD 1 Period 1 only 29,97,98
PER.1DAYSMON Monday in Period No/Yes PER1MON Yes 97,98
PER.1DAYSTUE Tuesday in Period No/Yes PER1TUE Yes 97,98
PER.1DAYSWED Wednesday in Period No/Yes PER1WED Yes 97,98
PER.1DAYSTHU Thursday in Period No/Yes PER1THU Yes 97,98
PER.1DAYSFRI Friday in Period No/Yes PER1FRI Yes 98
PER.1DAYSSAT Saturday in Period No/Yes PER1SAT Yes 98
PER.1DAYSSUN Sunday in Period No/Yes PER1SUN Yes 98
PER.1DAYSHOL Holiday in Period No/Yes PER1HOL Yes 98
PER.1OCC Occupied from 0 to 6144 PER1_OCC 00:00 98
PER.1UNC Occupied to 0 to 6144 PER1_UNC 24:00 98
Repeated for periods 2 to 8 98
HOL.L LOCAL HOLIDAY SCHEDULES
HD.01 HOLIDAY SCHEDULE 01 98
HD.01MON Holiday Start Month 0 to 12 HOL_MON1 98
HD.01DAY Start Day 0 to 31 HOL_DAY1 98
HD.01LEN Duration (Days) 0 to 99 HOL_LEN1 98
Repeated for holidays 2 to 30 98
DAY.S DAYLIGHT SAVINGS TIME
DS.ST DAYLIGHT SAVINGS START 98
DS.ST
ST.MN Month 1 to 12 STARTM 3 98
DS.ST
ST.WK Week 1 to 5 STARTW 2 98
DS.ST
ST.DY Day 1 to 7 STARTD 7 98
DS.STMIN.A Minutes to Add 0 to 90 MINADD 60 98
DS.SP DAYLIGHTS SAVINGS STOP
DS.SP
SP.MN Month 1 to 12 STOPM 11 98,99
DS.SPSP.WK Week 1 to 5 STOPW 1 98,99
DS.SP
SP.DY Day 1 to 7 STOPD 7 98,99
DS.SP
MIN.S Minutes to Subtract 0 to 90 MINSUB 60 98,99
ITEM EXPANSION RANGE UNITS CCN POINT
SYS.M ascii string spelling out the system mode string
HVAC ascii string spelling out the hvac modes string
CTRL ascii string spelling out the "control type" string
MODE MODES CONTROLLING UNIT
OCC Currently Occupied Off/On MODEOCCP
T.OVR Timed Override in Effect Off/On MODETOVR
DCV DCV Resetting Min Pos Off/On MODEADCV
SA.R Supply Air Reset Off/On MODESARS
DMD.L Demand Limit in Effect Off/On MODEDMLT
T.C.ST Temp.Compensated Start Off/On MODETCST
IAQ.P IAQ Pre-Occ Purge Active Off/On MODEIQPG
LINK Linkage Active - CCN Off/On MODELINK
LOCK Mech.Cooling Locked Out Off/On MODELOCK
H.NUM HVAC Mode Numerical Form 0 to 40 MODEHVAC
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
CURR CURRENTLY ACTIVE ALARMS
this is a dynamic list of active alarms
R.CUR Reset All Current Alarms No/Yes ALRESET ram config
HIST ALARM HISTORY
this is a record of the last 20 alarms