APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
HMZR
HVAC Mode..............: 16-char ASCII
HumidiMizer Capacity % HMZRCAPC
Condenser EXV Position % COND_EXV
Bypass EXV Position % BYP_EXV
HumidiMizer 3-way Valve Off/On HUM3WVAL
Cooling Control Point degF COOLCPNT
Evaporator Discharge Tmp degF EDT
Heating Control Point degF HEATCPNT
Leaving Air Temperature degF LAT
MODEDISP
System Mode............: 24-char ASCII
HVAC Mode..............: 16-char ASCII
Control Mode...........: 16-char ASCII
Currently Occupied Off/On MODEOCCP
Timed Override in effect Off/On MODETOVR
DCV resetting min pos Off/On MODEADCV
Supply Air Reset Off/On MODESARS
Demand Limit in Effect Off/On MODEDMLT
Temp.Compensated Start Off/On MODETCST
IAQ pre-occ purge active Off/On MODEIQPG
Linkage Active - CCN Off/On MODELINK
Mech.Cooling Locked Out Off/On MODELOCK
HVAC Mode Numerical Form MODEHVAC
MODETRIP
Unoccup. Cool Mode Start degF UCCLSTRT
Unoccup. Cool Mode End degF UCCL_END
Occupied Cool Mode Start degF OCCLSTRT
Occupied Cool Mode End degF OCCL_END
Ctl.Temp RAT,SPT or ZONE degF CTRLTEMP
Occupied Heat Mode End degF OCHT_END
Occupied Heat Mode Start degF OCHTSTRT
Unoccup. Heat Mode End degF UCHT_END
Unoccup. Heat Mode Start degF UCHTSTRT
HVAC Mode..............: 16-char ASCII
Unoccup. Cool Mode Start degF UCCLSTRT
TEMPCTRL
Evaporator Discharge Tmp degF EDT
Leaving Air Temperature degF LAT
Mixed Air Temperature degF MAT
Controlling Return Temp degF RETURN_T forcible
Controlling Space Temp degF SPACE_T forcible
TEMPS
Air Temp Lvg Supply Fan degF SAT
Return Air Temperature degF RAT forcible
Outside Air Temperature degF OAT forcible
Space Temperature degF SPT forcible
Space Temperature Offset deltaF SPTO forcible
Staged Heat LAT Sum degF LAT_SGAS
Staged Heat LAT 1 degF LAT1SGAS
Staged Heat LAT 2 degF LAT2SGAS
Staged Heat LAT 3 degF LAT3SGAS
Staged Gas Limit Sw.Temp degF LIMSWTMP
Air Temp Lvg Evap Coil degF CCT forcible
Cir A Sat.Condensing Tmp degF SCTA
Cir B Sat.Condensing Tmp degF SCTB
Cir A Sat.Suction Temp. degF SSTA
Cir B Sat.Suction Temp. degF SSTB
Cir A EXV1 Suction Temp. degF CASTEXV1
Cir A EXV2 Suction Temp. degF CASTEXV2
Cir B EXV1 Suction Temp. degF CBSTEXV1
Cir B EXV2 Suction Temp. degF CBSTEXV2
Cir A EXV1 Superheat Tmp deltaF SH_A1
Cir A EXV2 Superheat Tmp deltaF SH_A2
Cir B EXV1 Superheat Tmp deltaF SH_B1
Cir B EXV2 Superheat Tmp deltaF SH_B2
Cir A Subcooling Temp. deltaF SC_A
Cir B Subcooling Temp. deltaF SC_B
TSTAT
Control Mode...........: 16-char ASCII
Thermostat Y1 Input Off/On Y1 forcible
Thermostat Y2 Input Off/On Y2 forcible
Thermostat W1 Input Off/On W1 forcible
Thermostat W2 Input Off/On W2 forcible
Thermostat G Input Off/On G forcible