APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
UOUTPUT2
HEATING
Heat Relay 1 Off/On HS1
Modulating Heat Capacity % HTMG_CAP
Heat Relay 2 Off/On HS2
Relay 3 W1 Gas Valve 2 Off/On HS3
Relay 4 W2 Gas Valve 2 Off/On HS4
Relay 5 W1 Gas Valve 3 Off/On HS5
Relay 6 W2 Gas Valve 3 Off/On HS6
Relay 7 W1 Gas Valve 4 Off/On HS7
Relay 8 W2 Gas Valve 4 Off/On HS8
Relay 9 W1 Gas Valve 5 Off/On HS9
Relay 10 W2 Gas Valve 5 Off/On HS10
Heat Interlock Relay Off/On HIR forcible
Heat Reclaim Relay Off/On HTRCLRLY
ACTUATORS
Econ 1 Out Act Curr Pos % ECONRPOS
Econ 1 Out Cmd Position % ECONCPOS forcible
Econ 2 Ret Act Curr Pos % ECN2RPOS
Econ 2 Ret Cmd Position % ECN2CPOS forcible
Humidifier Act.Curr.Pos. % HUMDRPOS
Humidifier Command Pos. % HUMDCPOS
Ht.Coil Act.Current Pos. % HTCLRPOS
Ht.Coil Command Position % HTCLCPOS
Econ 3 Out Act.Curr.Pos. % ECN3RPOS
Econ 3 Out Cmd Position % ECN3CPOS forcible
GENERAL OUTPUTS
Humidifier Relay Off/On HUMIDRLY
UV-C Lamp Relay Off/On UVC_LAMP
Remote Alarm/Aux Relay Off/On ALRM forcible
VFD_DATA
VFD1 Status Word 1 VFD1STAT
VFD1 Actual Speed % % VFD1_SPD
VFD1 Actual Motor RPM VFD1RPM
VFD1 Actual Motor Freq VFD1FREQ
VFD1 Actual Motor Amps amps VFD1AMPS
VFD1 Actual Motor Torque % VFD1TORQ
VFD1 Actual Motor Power kW VFD1PWR
VFD1 DC Bus Voltage volts VFD1VDC
VFD1 Output Voltage volts VFD1VOUT
VFD1 Transistor Temp (C) VFD1TEMP
VFD1 Cumulative Run Time hours VFD1RUNT
VFD1 Cumulative kWh VFD1KWH
VFD1 Last Fault Code VFD1LFC
VFD1 DI1 State Open/Close VFD1_DI1 forcible
VFD1 DI2 State Open/Close VFD1_DI2 forcible
VFD1 DI3 State Open/Close VFD1_DI3 forcible
VFD1 DI4 State Open/Close VFD1_DI4 forcible
VFD1 DI5 State Open/Close VFD1_DI5 forcible
VFD1 DI6 State Open/Close VFD1_DI6 forcible
VFD1 AI1 (% of range) % VFD1_AI1 forcible
VFD1 AI2 (% of range) % VFD1_AI2 forcible
VFD2 Status Word 1 VFD2STAT
VFD2 Actual Speed % VFD2_SPD
VFD2 Actual Motor RPM VFD2RPM
VFD2 Actual Motor Freq VFD2FREQ
VFD2 Actual Motor Amps amps VFD2AMPS
VFD2 Actual Motor Torque % VFD2TORQ
VFD2 Actual Motor Power kW VFD2PWR
VFD2 DC Bus Voltage volts VFD2VDC
VFD2 Output Voltage volts VFD2VOUT
VFD2 Transistor Temp (C) VFD2TEMP
VFD2 Cumulative Run Time hours VFD2RUNT
VFD2 Cumulative kWh VFD2KWH
VFD2 Last Fault Code VFD2LFC
VFD2 DI1 State Open/Close VFD2_DI1 forcible
VFD2 DI2 State Open/Close VFD2_DI2 forcible
VFD2 DI3 State Open/Close VFD2_DI3 forcible
VFD2 DI4 State Open/Close VFD2_DI4 forcible
VFD2 DI5 State Open/Close VFD2_DI5 forcible
VFD2 DI6 State Open/Close VFD2_DI6 forcible
VFD2 AI1 (% of range) % VFD2_AI1 forcible
VFD2 AI2 (% of range) % VFD2_AI2 forcible