APPENDIX B — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
SUMZ
Cooling Control Point degF COOLCPNT
Mixed Air Temperature degF MAT
Evaporator Discharge Tmp degF EDT
Return Air Temperature degF RAT forcible
Outside Air Temperature degF OAT forcible
Econ 1 Out Act.Curr.Pos. % ECONOPOS
Econ 2 Ret Act.Curr.Pos. % ECON2POS
Econ 3 Out Act.Curr.Pos. % ECON3POS
Capacity Threshold Adjst Z_GAIN config
Capacity Load Factor SMZ
Next Stage EDT Decrease ADDRISE
Next Stage EDT Increase SUBRISE
Rise Per Percent Capacty RISE_PCT
Cap Deadband Subtracting Y_MINUS
Cap Deadband Adding Y_PLUS
Cap Threshold Subracting Z_MINUS
Cap Threshold Adding Z_PLUS
High Temp Cap Override Off/On HI_TEMP
Low Temp Cap Override Off/On LOW_TEMP
Pull Down Cap Override Off/On PULLDOWN
Slow Change Cap Override Off/On SLO_CHNG
SYSTEM
Reset All Current Alarms No/Yes ALRESET
Reset Alarm History No/Yes ALHISCLR
Reset the Device No/Yes RESETDEV
Local Machine Disable No/Yes UNITSTOP config
Soft Stop Request No/Yes SOFTSTOP forcible
Emergency Stop Enable/EMStop EMSTOP forcible
CEM AN4 10K temp J5,7-8 degF CEM10K1 forcible
CEM AN5 10K temp J5,9-10 degF CEM10K2 forcible
CEM AN6 10K tmp J5,11-12 degF CEM10K3 forcible
CEM AN1 10K temp J5,1-2 degF CEM10K4 forcible
CEM AN4 4-20 ma J5,7-8 milliAmps CEM4201 forcible
CEM AN1 4-20 ma J5,1-2 milliAmps CEM4204 forcible
TESTACTC
Econ 1 Out Act.Cmd.Pos. % ECON1TST
Economizer Calibrate Cmd No/Yes ECONOCAL
Econ 1 Out Act Ctl Angle ECONCANG
Econ 2 Ret Act.Cmd.Pos. % ECON2TST
Economzr 2 Calibrate Cmd No/Yes ECON2CAL
Econ2 Ret Act Ctl Angle ECN2CANG
Econ 3 Out Act.Cmd.Pos. % ECON3TST
Economzr 3 Calibrate Cmd No/Yes ECON3CAL
Econ3 Out Act Ctl Angle ECN3CANG
Ht.Coil Command Position % HTCLACTS
Heating Coil Act.Cal.Cmd No/Yes HCOILCAL
Heat Coil Act.Ctl.Angle HTCLCANG
Humidifier Command Pos. % HUMD_TST
Humidifier Act. Cal. Cmd No/Yes HUMIDCAL
Humidifier Act.Ctrl.Ang. HUMDCANG
TESTCOOL
Econ 1 Out Act.Cmd.Pos. % ECONCOOL
Static Pressure Setpoint in H2O SPSPCTST
Requested Cool Stage CLST_TST
Compressor A1 Relay Off/On CMPA1TST
Minimum Load Valve Relay Off/On MLV_TST
Compressor A1 Capacity % A1CAPTST
Two Circuit Start A1,B1 Off/On CMPABTST
Compressor A2 Relay Off/On CMPA2TST
Compressor A3 Relay Off/On CMPA3TST
Compressor A4 Relay Off/On CMPA4TST
Compressor B1 Relay Off/On CMPB1TST
Compressor B2 Relay Off/On CMPB2TST
Compressor B3 Relay Off/On CMPB3TST
Compressor B4 Relay Off/On CMPB4TST
HumidiMizer 3-way Valve Off/On RHVC_TST
Condenser EXV Position % CEXVCTST
Bypass EXV Position % BEXVCTST
TESTEXVS
Circuit A EXV 1 Position % A_X1_TST
Circuit A EXV 2 Position % A_X2_TST
Circuit B EXV 1 Position % B_X1_TST
Circuit B EXV 2 Position % B_X2_TST
Cir A EXV 1 Calibrate Off/On A_X1_CAL
Cir A EXV 2 Calibrate Off/On A_X2_CAL
Cir B EXV 1 Calibrate Off/On B_X1_CAL
Cir B EXV 2 Calibrate Off/On B_X2_CAL