APPENDIX F — BACNET COMMUNICATION OPTION (cont)
NETWORK POINTS LIST (cont)
See legend on page 233.
POINT DESCRIPTION CCN POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Space Temperature Offset SPTO R/W °^F -10 - 10 AV:138 spto_1
SPT Override Enabled ? SPT_OVER W Yes 0 - 1 BV:54 spt_over_1
SPT Sensor SPT_SEN_VALID R BV:8 spt_sen_valid
Staged Gas Capacity Calc HTSGCALC R % AV:75 htsgcalc_1
Staged Gas LAT 1 LAT1SGAS R °F AV:150 lat1sgas_1
Staged Gas LAT 2 LAT2SGAS R °F AV:151 lat2sgas_1
Staged Gas LAT 3 LAT3SGAS R °F AV:152 lat3sgas_1
Staged Gas LAT Sum LAT_SGAS R °F AV:153 lat_sgas_1
Staged Gas Limit Sw Temp LIMSWTMP R °F AV:154 limswtmp_1
Stat. Pres. Reset Config SPRSTCFG R/W 0 0 - 4 AV:156 sprstcfg_1
Static Pressure BP R H20 AV:1016 bldg_static_press_1
Static Pressure Reset SPRESET R/W 0 - 15 AV:157 spreset_1
Static Pressure Setpoint SPSP W “H2O 1.5 0 - 5 AV:3050 sa_static_stpt_1
Static Pressure Transducer
Failure T211 R BV:116 t211_1
Supply Air CFM SACFM R CFM 0 - 50000 AV:78 sacfm_1
Supply Air Reset MODESARS R 0 - 1 BV:93 modesars_1
Supply Air Setpnt. Reset SASPRSET R/W °^F 0 - 20 AV:158 sasprset_1
Supply Air Setpoint SASP W °F 45 - 75 AV:3007 sa_temp_stpt_1
Supply Fan Bypass Input SFBYIN R BV:82 sfbyin_1
Supply Fan Bypass Relay SFBYRLY R BV:83 sfbyrly_1
Supply Fan not on 30s ? SFONSTAT R 0 - 1 BV:22 sfonstat_1
Supply Fan Request SFANFORC W 0 - 1 BV:2004 sfan_forc_1
Supply Fan Status Switch SFS W 0 - 1 BV:95 sfs_1
Supply Fan VFD Speed SFAN_VFD R % 0 - 100 AV:2050 sf_vfd_output_1
System Cooling Demand Level R AV:9006 cool_demand_level_1
System Demand Limiting R BV:7 dem_lmt_act_1
System Heating Demand Level R AV:9036 heat_demand_level_1
System OAT Master R dF AV:80001 mstr_oa_temp_1
Temp Comp Start Cool Factor TCSTCOOL R/W min 0 0 - 60 AV:159 tcstcool_1
Temp Comp Start Heat Factor TCSTHEAT R/W min 0 0 - 60 AV:160 tcstheat_1
Temp Compensated Start MODETCST R 0 - 1 BV:96 modetcst_1
Temper Supply Air Setpt SASPTEMP R/W °F 35 - 70 AV:15 sasptemp_1
Temper Vent Unocc TEMPVUNC R/W °^F -20 - 80 AV:164 tempvunc_1
Tempering in Cool SASP TEMPCOOL R/W °^F 5 - 75 AV:161 tempcool_1
Tempering Purge SASP TEMPPURG R/W °^F -20 - 80 AV:162 temppurg_1
Tempering Vent Occ SASP TEMPVOCC R/W °^F -20 - 80 AV:163 tempvocc_1
Thermostat G Input G W 0 - 1 BV:1021 g_input_1
Thermostat W1 Input W1 W 0 - 1 BV:1019 w1_input_1
Thermostat W2 Input W2 W 0 - 1 BV:1020 w2_input_1
Thermostat Y1 Input Y1 W 0 - 1 BV:1017 y1_input_1
Thermostat Y2 Input Y2 W 0 - 1 BV:1018 y2_input_1
Timed Override In Effect MODETOVR R BV:97 modetovr_1
Timed-Override in Effect OVERLAST R BV:98 overlast_1
Un.Ec.Free Cool OAT Lock UEFCNTLO R/W °F 50 40 - 70 AV:166 uefcntlo_1
Unit Down Due to Failure A152 R BV:117 a152_1
Unoc Econ Free Cool Cfg UEFC_CFG R/W 0 0 - 720 AV:172 uefc_cfg_1
Unoc Econ Free Cool Time UEFCTIME W min 120 AV:173 uefctime_1
Unoccupied Cool Mode End UCCL_END R °F 0 - 100 AV:168 uccl_end_1
Unoccupied Cool Mode Start UCCLSTRT R °F 0 - 100 AV:169 ucclstrt_1
Unoccupied Cooling Setpoint LINK_UCSP R/W AV:2604 link_ucsp_1
Unoccupied Heat Mode End UCHT_END R °F 0 - 100 AV:170 ucht_end_1
Unoccupied Heat Mode Start UCHTSTRT R °F 0 - 100 AV:171 uchtstrt_1
Unoccupied Heating Setpoint LINK_UHSP R/W AV:2605 link_uhsp_1
User Defined Analog 1 W AV:2901 user_analog_1_1
User Defined Analog 2 W AV:2902 user_analog_2_1
User Defined Analog 3 W AV:2903 user_analog_3_1
User Defined Analog 4 W AV:2904 user_analog_4_1
User Defined Analog 5 W AV:2905 user_analog_5_1
User Defined Binary 1 W BV:2911 user_binary_1_1
User Defined Binary 2 W BV:2912 user_binary_2_1
User Defined Binary 3 W BV:2913 user_binary_3_1
User Defined Binary 4 W BV:2914 user_binary_4_1
User Defined Binary 5 W BV:2915 user_binary_5_1